Specifi cations
Power Required
None - self powered
Output Switch
Isolated Solid State Switch
Switch Rating
DODC - N.O. 1A @ 30VDC
Off State Leakage
<10 Microamps
Response Time
100 mS
Hysteresis
< 8% of Setpoint
Set Point Ranges
A Contact: Adjustable 0.75A - 20A
B Contact: Adjustable 0.75A - 20A
Start-up Delay
2.0 Seconds (fi xed)
Setpoint Adjust
4 Turn potentiometer
Isolation Voltage
Designed to meet UL508 require-
ments to 1,270 VAC
Tested to 5,000 VAC
Frequency Range
6-100Hz
Sensing Apeture
-FL 0.75" (19mm)
Environmental
-4 to122Deg F (-20 to 50 Deg C)
0-95% RH, Non Condensing
Ranges & Maximum Amps
TYPE
RANGE
MAXIMUM INPUT AMPS
CONTINUOUS
FIXED CORE
0.75- 20 A
50A
FIXED CORE
20-50 A
50A
Model Number Key
AS1 - DODC - FL
OUTPUT
DODC - Dual Normally Open, 1.0A @ 30VDC
SENSOR TYPE:
AS1 - AC current operated switch with single range
0.75A -- 20A
AS2 - AC current operated switch with single range
20A -- 50A
Know Your Power
Other NK Technologies Products Include:
AC & DC Current Transducers
AC & DC Current Operated Switches
1φ & 3φPower Transducers
6 SEC.
1 SEC.
Current & Potential Transformers (CTs&PTs)
200A
400A
200A
400A
3511 Charter Park Drive, San Jose, CA 95136
800-959-4014 or +1-408-871-7510 Phone
+1-408-871-7515 FAX
sales@nktechnologies.com, www.nktechnologies.com
CASE STYLE:
FL - Fixed Core, Top Terminals
:
(Solid State Switch)
INSTRUCTIONS
AS1 DODC SERIES
AC Current Operated Switch
With Dual Output
Quick "How To" Guide
1. Run the wire to be monitored through
aperture.
2. Mount the sensor.
3. Connect output wiring.
A. Use up to 14 AWG copper wires.
B. Ensure load matches the output shown on
the sensor label.
4. Adjust Setpoint
A. Use the potentiometer to adjust the set-
point.
AS1-DODC-FL Inst. Rev 2 12/14 P/N 39-360-0001

Advertisement

loading

Summary of Contents for NK TECHNOLOGIES AS1 - DODC - FL

  • Page 1 Specifi cations Model Number Key Power Required None - self powered AS1 - DODC - FL Output Switch Isolated Solid State Switch Switch Rating DODC - N.O. 1A @ 30VDC INSTRUCTIONS Off State Leakage <10 Microamps Response Time 100 mS...
  • Page 2 Description Output Wiring AS1 Series are self-powered, solid-state current-operated Connect control or monitoring wires to the sensor. Use Startup switches which trigger when the current level sensed up to 14 AWG copper wire and tighten terminals to 5 Inrush through the aperture exceeds the adjusted setpoint. The solid inch-pounds torque.