4. Use a puller or slide hammer to remove the end
bracket. The end bracket has two 1/4 in. threaded
holes, four inches apart, for use with an adapter
bar. See Figure 6-2.
5. Remove the 4 socket head screws that secure the
stator. See Figure 6-3.
6. Grasp the stator firmly. Pull straight out to prevent
damage to the stator laminations. See Figure 6-4.
7. Loosen the thrubolt. See Figure 6-5.
8. Loosen the rotor/fan assembly by lightly tapping on
alternate sides with a rubber mallet. Use only a
rubber mallet to prevent damage to the bolt.
9. Remove the thrubolt and rotor.
1
1. End bracket
2. Two 1/4-20 in. holes, four inches apart, for use with slide
hammer or puller
3. Slide hammer
4. Adapter with long bolts attached to end bracket 1/4 in.
holes
Figure 6-2 Remove End Bracket
Figure 6-3 Remove Socket Head Screws
38
Section 6 Disassembly/Reassembly
2
3
4
Figure 6-4 Remove Stator
1
Figure 6-5 Loosen Thrubolt