5.1.3
Remote Start/Stop Connections
Set the generator set master switch to the AUTO
position for remote operation. For remote starting and
stopping, use a three-wire start/stop switch connected
to the controller harness. To start the generator set,
open a contact between pins 6 (N) and 7 (STT) on the
controller harness connector and close a contact
between connector pins 5 (STP) and 6 (N) (see the
wiring diagram in Section 7). Close the contact between
pins 6 and 7 to stop the generator set.
5.1.4
Control Connections
Wiring harnesses connect the generator set control
board to the remote controls and the engine. The
generator set Operation Manual, TP-6119, shows the
engine, sensing, and controller wiring harnesses. The
wiring diagram in Section 7 shows the harness
connections. Figure 5-2 defines the abbreviations used
in the wiring diagram.
5.1.5
Resetting the Controller
Move the generator set master switch to the STOP
position and then release it to reset the controller. Reset
the controller after applying power for the first time or to
clear a fault condition. See Section 5.1.6 for more
information about faults.
Note: If the power to the controller has been
disconnected and reconnected, the controller will
require resetting.
32
Section 5 Controller Operation and Test
Abbreviation
Definition
70
Run
71
Crank
AC1
Speed sensing
AC2
Speed sensing
BCA
Battery charging alternator
DCN
DC negative
DCP
DC positive
EBG
Engine block ground
GV
Gas valve
HOT
High oil temperature switch
HR
Hourmeter
LOP
Low oil pressure switch
M1
Throttle control
M2
Throttle control
M3
Throttle control
M4
Throttle control
N
Ground
N/C
Not connected
OVC
Overcrank
OVS
Overspeed
OVT
Overtemperature
P
Positive
QCON
Quick connect terminal
RECT
Rectifier (voltage)
SM
Starter motor
SR
Starter relay
SS
Starter solenoid
Stat
Stator
STM
Stepper motor (governor)
STP
Stop
STT
Start
Figure 5-2 Wiring Diagram Abbreviations