208v ~ 60hz 25a

Advertisement

Ensure that the supply cables, circuit breakers and other electrical
installation equipment are correctly sized for the
DTAC being installed, see Table 1. For each DTAC a single phase local
isolator with a contact separation on both poles of at least 3mm must be
fitted to the supply wiring (the isolator must be fitted within an
accessible position). The DTAC should be connected to a 208V 2-pole
AC 60Hz electrical supply and must be earthed. Remove the two outer
M4 x 12mm pan head Philips screws atop the DTAC and release the
power connector plate. Fit cable gland to power connector plate. Insert
electrical supply cable via cable gland (see Figure 5) and tighten gland
around cable.
Figure 5: Electrical Connection
Connect each of the cables as follows:
Live brown cable to terminal marked L or L1
Neutral blue cable to terminal marked N or L2
Earth green/yellow cable to terminal marked PE
Position the electrical supply cables as they come out of the terminal
block as shown in Figure 5. Ensure only sufficient cable is pulled
through to enable connection to terminal block and to avoid excess
cable coming into contact with any moving parts. Carefully insert all
cables through the rectangular hole in the top of the DTAC and refit the
power connector plate. Ensure mains supply cable is correctly and
sufficiently strained by the plastic cable gland.
208V AC 60Hz
JET 3 2.25/1.125 kW
L N E
JET 6
4.91/2.455 kW
Figure 6: Jet 6 Wiring Diagram
OPERATION
Control of the DTAC is achieved by using the three integral switches
mounted adjacent to the discharge grille.
Switch
I
I + Middle
I + Middle + End Fan + full heat
The DTAC panels are coated in an easy to peel protective film. Please
ensure all the protective film is removed before the DTAC is put into
service. Before leaving site it is important that the sliding window DTAC
installation and these instructions are "Handed-Over" to the end user or
their representative and the operation of it is fully explained and that
they understand how it operates.
THERMAL SAFETY CUT
If the DTAC exceeds normal operating temperature the thermal safety
cut-outs will operate and isolate electrical supply to the heating
elements. Thermoscreens recommend only competent qualified
persons service the DTAC.
To reset the thermal safety cut-outs disconnect electrical supply to the
DTAC, determine and resolve the cause of the fault. Allow DTAC
sufficient time to cool before restoring supply. If the fault persists
arrange for a competent technician to attend site and investigate. In
order to avoid a hazard due to inadvertent resetting of the thermal cut-
out, this appliance must not be supplied through an external switching
device, such as a timer, or connected to a circuit that is regularly
switched on and off by the utility.
SERVICE
Always disconnect and isolate the main electrical supply before
installing, maintaining or repairing this equipment. All
maintenance/repairs should only be carried out by a competent
electrician or Thermoscreens appointed technician. To ensure the
DTAC operates efficiently, the air inlet and outlet grilles, fan impellers,
housings and motors must be kept free of dust and debris. Regularly
vacuum and clean any build-up of dirt and debris within the DTAC
(please note that the motor is permanently lubricated and require no
additional lubrication). Once the DTAC has been cleaned check all
electrical connections within the unit ensuring terminals are tight and
that crimped connections have not become loose. If the outer casing
requires cleaning this should be carefully done using a warm soft cloth.
Do not use solvents or abrasive materials. Reconnect the electrical
supply and fully function test the DTAC to ensure correct operation.
WARRANTY
If any problems are encountered, please contact your installer or
supplier. All units are covered by a one year warranty. Subject to
availability we undertake to repair or exchange this product.
Care has been taken in compiling these instructions to ensure they are
correct, although Thermoscreens disclaims all liability for damage
resulting from any inaccuracies and/or deficiencies in this
documentation. Thermoscreens retain the right to change the
specifications stated in these instructions.
Action
Fan on
Fan + half heat
2
Toll Free: 877 445 3739 Tel: 705 797 0007 Fax: 705 797 0013
e-mail:
-
OUTS
&
MAINTENANCE
Conforms to: CAN CSA-C22.2 no.46-13 & UL 2021(Ed.3): 2013