IFM Electronic efector 300 Operating Instructions Manual

IFM Electronic efector 300 Operating Instructions Manual

Compressed air meters
Table of Contents

Advertisement

Quick Links

Operating instructions
Compressed air meters
UK
SD5100
SD6100
SD8100

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the efector 300 and is the answer not in the manual?

Questions and answers

Summary of Contents for IFM Electronic efector 300

  • Page 1 Operating instructions Compressed air meters SD5100 SD6100 SD8100...
  • Page 2: Table Of Contents

    Contents 1 Preliminary note ���������������������������������������������������������������������������������������������������4 1�1 Symbols used ������������������������������������������������������������������������������������������������4 2 Safety instructions �����������������������������������������������������������������������������������������������4 3 Functions and features ����������������������������������������������������������������������������������������5 4 Function ���������������������������������������������������������������������������������������������������������������6 4�1 Process measured signals ����������������������������������������������������������������������������6 4�2 Volumetric flow monitoring �����������������������������������������������������������������������������6 4�3 Consumed quantity monitoring (totaliser function) ����������������������������������������6 4�3�1 Consumed quantity monitoring with pulse output ���������������������������������7 4�3�2 Consumed quantity monitoring with preset counter �����������������������������7 4�4 Temperature monitoring ���������������������������������������������������������������������������������7 4�5 Volumetric flow or temperature monitoring / switching function ���������������������8...
  • Page 3 10�1�3 Parameter setting tools ���������������������������������������������������������������������20 10�2 Parameter setting in general ���������������������������������������������������������������������21 10�2�1 Change from menu level 1 to menu level 2: �������������������������������������21 10�2�2 Locking / unlocking ���������������������������������������������������������������������������22 10�2�3 Timeout ���������������������������������������������������������������������������������������������22 10�3 Settings for consumed quantity monitoring �����������������������������������������������22 10�3�1 Configure limit value monitoring with OUT1 �������������������������������������22 10�3�2 Configure limit value monitoring with OUT2 �������������������������������������23 10�3�3 Configure analogue value for volumetric flow �����������������������������������23 10�4 Settings for consumed quantity monitoring �����������������������������������������������23...
  • Page 4: Preliminary Note

    11�5 General operating conditions ���������������������������������������������������������������������30 12 Technical data and scale drawing ��������������������������������������������������������������������30 13 Factory setting �������������������������������������������������������������������������������������������������31 1 Preliminary note 1.1 Symbols used ► Instructions > Reaction, result […] Designation of keys, buttons or indications → Cross-reference Important note Non-compliance can result in malfunction or interference� Information Supplementary note�...
  • Page 5: Functions And Features

    liability for consequences of misuse by the operator� Improper installation and use of the devices results in a loss of the warranty claims� • Correct operation and compliance with the measurement accuracy can only be ensured if the environmental conditions specified in the technical data are adhered to�...
  • Page 6: Function

    4 Function 4.1 Process measured signals The unit displays the current process values� It generates 2 output signals according to the parameter setting� OUT1: 4 selection options Parameter setting - Switching signal for volumetric flow quantity limit value → 10.3.1 - or switching signal for flow velocity limit value → 10.3.1 - or pulse signal for quantity meter → 10.4.1...
  • Page 7: 4�3�1 Consumed Quantity Monitoring With Pulse Output

    • In addition the value before the last reset is saved� This value can also be displayed� The meter saves the totalled consumed quantity every 10 minutes� After a power failure this value is available as the current meter reading� If a time-controlled reset is set, the elapsed time of the set reset interval is also saved�...
  • Page 8: 4�5 Volumetric Flow Or Temperature Monitoring / Switching Function

    4.5 Volumetric flow or temperature monitoring / switching function OUTx changes its switching status if it is above or below the set switching limits (SPx, rPx)� The following switching functions can be selected: 4.5.1 Hysteresis function Normally open: [OUx] = [Hno] Normally closed: [OUx] = [Hnc] First the set point (SPx) is set, then the reset point (rPx) with the requested...
  • Page 9: 4�6 Volumetric Flow Or Temperature Monitoring / Analogue Function

    4.6 Volumetric flow or temperature monitoring / analogue function -30% -20% 100% 120% 130% Characteristics of the analogue output according to the standard IEC 60947-5-7 1: Output current in mA 2: Operating area 3: Measuring range 4: Range between analogue start point and analogue end point 5: Error message [Err�] is displayed 6: Final value of the measuring range (VMR) 7: Error message [OL] is displayed (= overload)
  • Page 10: 4�7 Set Standard Conditions Of The Volume Flow

    4.7 Set standard conditions of the volume flow The unit is adjusted to a standard volume flow to DIN ISO 2533, i�e� volume flow at 1013 hPa, 15 °C and 0 % relative air humidity� The unit can be set to different standard conditions: • Via the menu item [rEF�P] the standard pressure is set, which serves as a refer- ence for the measured and display values for volumetric flow (→ 10.6.5).
  • Page 11: Installation

    5 Installation ► The rules and regulations for the installation and operation of com- pressed air equipment must be observed� 5.1 Installation location ► Install the unit downstream of the cold dryer� ► Install the unit near the load� ► If compressed air is fed into the main pipe through parallel pipes: mount the unit in the main pipe�...
  • Page 12: 5�3 Installation Position

    5.3 Installation position • Permitted installation positions: pipe length vertical, any position (fig� 1, 2); pipe length horizontal, unit vertical (fig� 3, 5), unit on side, pipe length left (fig� 4)� • Avoid the installation position in fig� 6 (unit on side, pipe length right)� If the flow rate is low, the specified measurement accuracy cannot be adhered to�...
  • Page 13: 5�4 Installation In Pipes

    SD6100, SD8100: 5.4 Installation in pipes ► Fit the unit in the pipe in accordance with the flow direction (arrow on the unit) and tighten� SD5100: SD6100; SD8100:...
  • Page 14: Electrical Connection

    6 Electrical connection The unit must be connected by a qualified electrician� The national and international regulations for the installation of electrical equipment must be adhered to� Voltage supply according to EN 50178, SELV, PELV� ► Disconnect power� ► Connect the unit as follows: BK: black BN: brown OUT2...
  • Page 15: Operating And Display Elements

    7 Operating and display elements 1 to 8: Indicator LEDs • LEDs 1-6 = unit of the currently represented numerical value → 11.1 Reading the process value • LED 7 = switching status of output OUT2 / of input InD • LED 8 = switching status of output OUT1 9: Alphanumeric display, 4 digits • Current volumetric flow quantity (with setting [SELd] = [FLOW]) • Current flow velocity (with setting [SELd] = [FLOW]) • Meter reading of the totaliser (with setting SELd = TOTL) • Current medium temperature (with setting SELd = TEMP)
  • Page 16: Menu

    8 Menu 8.1 Main menu Nl/min Nm/s °C  Mode/Enter ↓ Extended functions...
  • Page 17 Explanation main menu SP1 / rP1 Upper / lower limit value for volumetric flow� ImPS Pulse value� Pulse repetition active (= pulse output) or not active ImPR (= preset counter function)� Output function for OUT1 (volumetric flow or consumed quantity): - Switching signal for the limit values�...
  • Page 18: 8�2 Extended Functions

    8.2 Extended functions ↑ Main menu...
  • Page 19: Set

    Explanation extended functions HI / LO Maximum / minimum value memory for volumetric flow� FOU1 Status of output 1 in case of an internal fault� FOU2 Status of output 2 in case of an internal fault� Measured value damping / damping constant in seconds� Meter reset: manual reset / time-controlled reset�...
  • Page 20: Parameter Setting

    10 Parameter setting The selection of an incorrect medium increases the measurement deviation� ► Set the medium first before using the unit for the first time and setting all the other parameter values (→ 10.6.8 Select the medium to be monitored)� Parameters can be set before installation and set-up of the unit or during opera- tion�...
  • Page 21: 10�2 Parameter Setting In General

    10.2 Parameter setting in general 3 steps must be taken for each parameter setting: Select parameter ► Press [Mode/Enter] until the re- Mode/EnterSet quested parameter is displayed� Set parameter value ► Press and hold [Set]� > Current setting value of the param- Mode/EnterSet eter flashes for 5 s�...
  • Page 22: 10�2�2 Locking / Unlocking

    ► Briefly press [Set]� > The first parameter of the submenu is Mode/EnterSet displayed (here: [HI])� 10.2.2 Locking / unlocking The unit can be locked electronically to prevent unintentional settings� ► Make sure that the unit is in the normal operating mode�...
  • Page 23: 10�3�2 Configure Limit Value Monitoring With Out2

    10.3.2 Configure limit value monitoring with OUT2 ► Select [Uni] and set the unit of measurement (→ 10.6.1). ► Select [SEL2] and set [FLOW]� ► Select [OU2] and set the switching function� - [Hno] = hysteresis function/normally open - [Hnc] = hysteresis function/normally closed - [Fno] = window function/normally open - [Fnc] = window function/normally closed ►...
  • Page 24: 10�4�3 Setting The Pulse Value

    10.4.3 Setting the pulse value ► Select [ImPS]� ► Press and hold [Set]� > The current numerical value flashes for 5 s, then one of the 4 digits becomes active and can be changed as below: 1� Briefly press [Set] >...
  • Page 25: 10�4�4 Manual Counter Reset

    10.4.4 Manual counter reset ► Select [rTo]� ► Press [Set] until [rES�T] is displayed� ► Briefly press [Mode/Enter]� > The counter is reset to zero� 10.4.5 Time-controlled counter-reset ► Select [rTo]� ► Press [Set] until the requested value is displayed (intervals from 1 hour to 8 weeks)�...
  • Page 26: 10�5 Settings For Temperature Monitoring

    10.5 Settings for temperature monitoring 10.5.1 Configure limit value monitoring with OUT2 ► Select [SEL2] and set [TEMP]� ► Select [OU2] and set the switching function� - [Hno] = hysteresis function/normally open - [Hnc] = hysteresis function/normally closed - [Fno] = window function/normally open - [Fnc] = window function/normally closed ►...
  • Page 27: 10�6�2 Configuration Of The Standard Display

    10.6.2 Configuration of the standard display ► Select [SELd] and determine the standard measuring unit� - [FLOW] = the current volumetric flow value in the standard unit of measurement is displayed - [TOTL] = the current meter reading in Nm or 1000 Nm - [TEMP] = the current medium temperature in °C is displayed ►...
  • Page 28: 10�6�6 Set Standard Temperature

    10.6.6 Set standard temperature ► Select [rEF�T] and set the requested standard temperature� Setting range: 0���25 °C in steps of 1 °C� 10.6.7 Set low flow cut-off ► Select [LFC] and set the limit value� Setting range: 0�1���0�8 Nm³/h in steps of 0�1 Nm³/h� 10.6.8 Select the medium to be monitored ►...
  • Page 29: Operation

    11 Operation 11.1 Reading the process value The LEDs 1-6 signal which process value is currently displayed� The process value to be displayed as standard (temperature, flow velocity or me- ter reading of the totaliser) can be preset → 10.6.2 Configuration of the standard display)� A standard unit of measurement can be defined for the flow velocity (Nl/min or /h or Nm/s → 10.6.1).
  • Page 30: 11�3 Read Set Parameters

    11.3 Read set parameters ► Press [Mode/Enter] until the requested parameter is displayed� ► Briefly press [Set]� > The unit displays the corresponding parameter value� > After about 15 s (from menu level 1) or 30 s (from menu level 2) it again dis- plays the parameter, then it returns to the Run mode�...
  • Page 31 13 Factory setting Factory setting User setting 20 % * 19.5 % * ImPS 0.001 ImPR 40 % * 39.5 % * ASP2 0 % * AEP2 100 % * FOU1 FOU2 nm3h SELd FLOW SEL2 FLOW rEF.P 1013hPa rEF.T 15 °C 0.25 % * MEDI...