CONSIDER SYSTEM REQUIREMENTS
• Consult local building codes and NEC for special instal-
lation requirements.
• Allow sufficient space for airflow clearance, wiring,
refrigerant piping, and unit servicing. See Fig. 2.
• Locate unit so that condenser airflow is unrestricted on all
sides and above. Refer to Fig. 2.
• Unit may be mounted on a level pad directly on base rails
or mounted on raised pads at support points. See Table 2
for weight distribution based on recommended support points.
NOTE: If vibration isolators are required for a particular in-
stallation, use corner weight information in Table 2 to make
proper selection.
Table 2 — Weight Distribution
WEIGHT CHART*
UNIT
Corner
Std Unit
38
W
Lb
Kg
Lb
Kg
AK007
340
154
86
39
AK008
370
168
86
39
AK012
395
179
89
40
AKS008
510
231
115
52
AKS009
564
256
133
60
AKS012
564
256
133
60
*Weights are for aluminum coils.
NOTES:
1. Dimensions in [ ] are in millimeters.
2. See Fig. 3 for additional information.
Step 2 — Rig and Mount the Unit
Be sure unit panels are securely in place prior to

rigging.

RIGGING — These units are designed for overhead rig-
ging. Refer to rigging label for preferred rigging method.
Spreader bars are not required if top crating is left on unit.
All panels must be in place when rigging. (See Fig. 3.) As
further protection for coil faces, plywood sheets may be placed
against sides of unit, behind cables. Run cables to a central
suspension point so that angle from the horizontal is not less
than 45 degrees. Raise and set unit down carefully.
If it is necessary to roll unit into position, mount unit on
rails, using a minimum of 3 rollers. Apply force to rails,
Corner
Corner
Corner
X
Y
Z
Lb
Kg
Lb
Kg
Lb
Kg
53
24
77
35
124
56
78
35
99
45
107
49
92
42
109
49
105
48
89
40
133
60
173
87
97
44
141
64
193
88
97
44
141
64
193
88
not unit. If unit is to be skidded into position, place it on a
large pad and drag it by the pad. Do not apply any force to
unit.
Raise from above to lift unit from rails or pad when unit
is in final position.
After unit is in position, remove all shipping materials and
top crating.
COMPRESSOR MOUNTING — Compressors are shipped
from the factory held down by 4 bolts. After unit is installed,
loosen each bolt until the snubber washer can be moved with
finger pressure. See Fig. 4.
Step 3 — Complete Refrigerant Piping Connec-
tions —
Suction connection is sweat with plastic cap;
liquid connection is sweat with plastic cap. Refer to
Table 3A or 3B for the proper line sizes. Follow standard
piping practices.
SIZE REFRIGERANT LINES — Consider length of piping
required between condensing unit and air handler, amount
of liquid lift, and compressor oil return. See Table 4A and
4B and also refer to Part 3 of Carrier System Design Manual
for design details and line sizing. Refer to air handler in-
stallation instructions for additional information.
Table 3A — Refrigerant Piping Sizes — 60 Hz
LINEAR LENGTH OF PIPING — FT (M)
0-25
(0-7.6)
UNIT
38
L
S
AK007
1
1
1
2
8
AK008
1
1
1
2
8
AK012
5
1
1
8
8
AKS008
1
1
1
2
8
AKS009
1
5
1
8
8
AKS012
5
1
1
8
8
LEGEND
L — Liquid Line
S — Suction Line
Table 3B — Refrigerant Piping Sizes — 50 Hz
LINEAR LENGTH OF PIPING — FT (M)
0-25
(0-7.6)
UNIT
38
L
S
AK007
1
1
1
2
8
AK008
1
1
1
2
8
AK012
5
1
1
8
8
AKS008
1
1
1
2
8
AKS009
1
5
1
8
8
AKS012
5
1
1
8
8
LEGEND
L — Liquid Line
S — Suction Line
NOTES FOR TABLES 3A AND 3B:
1. Pipe sizes are based on a 2 F (1 C) loss for liquid and suction lines.
2. Pipe sizes are based on the maximum linear length shown for each
column, plus a 50% allowance for fittings.
3. Charge units with R-22 in accordance with unit installation
instructions.
4. Line size conversion to mm is:
in.
mm
1
12.7
2
5
15.9
8
1
1
28.6
8
1
3
34.9
8
4
25-50
50-75
(7.6-15.2)
(15.2-22.9)
(22.9-30.5)
Line Size (in. OD)
L
S
L
S
L
1
1
1
1
1
1
1
2
8
2
8
1
1
1
5
1
1
5
2
8
8
8
5
1
3
5
1
3
5
8
8
8
8
1
1
1
5
1
1
5
2
8
8
8
1
1
5
1
5
3
5
8
8
8
8
5
1
1
5
1
3
5
8
8
8
8
25-50
50-75
(7.6-15.2)
(15.2-22.9)
(22.9-30.5)
Line Size (in. OD)
L
S
L
S
L
1
1
1
1
1
1
1
2
8
2
8
1
1
1
1
5
3
5
2
8
8
8
5
1
3
5
1
3
5
8
8
8
8
1
1
1
5
1
3
5
2
8
8
8
1
1
5
1
5
3
5
8
8
8
8
5
1
1
5
1
3
5
8
8
8
8
75-100
S
1
1
2
8
1
3
8
8
1
3
8
8
1
3
8
8
1
3
8
8
1
3
8
8
75-100
S
1
1
2
8
1
3
8
8
1
3
8
8
1
3
8
8
1
3
8
8
1
3
8
8