Altronix SMP7 Installation Manual
Altronix SMP7 Installation Manual

Altronix SMP7 Installation Manual

Power supply/charger

Advertisement

SMP7 power supply/charger converts converts a low voltage AC input into 12VDC or 24VDC output with a
Altronix
6A continuous supply current.
Input:
• Input 28VAC

(Voltage Output/Transformer Selection Table).

Output:
• 12VDC or 24VDC selectable output.
• 6A supply current.
• Output fuse is rated 15A/32V.
• Filtered and electronically regulated outputs.
• Short circuit and thermal overload protection.
Voltage Output/Transformer Selection Table:
Output VDC
Switch Position
12VDC
24VDC
SMP7 should be installed in accordance with The National Electrical Code and all applicable Local Regulations.
1. Mount SMP7 in the desired location/enclosure (mounting hardware included).
2. Set SMP7 to the desired DC output voltage by setting the SW1 switch (Fig. 1a, pg. 2) to the appropriate
position (Voltage Output/Transformer Selection Table).
Adjust output voltage by using the trimpot on the power supply board (Fig. 1a, pg. 2) prior to connecting devices.
3. Connect proper transformer to terminals marked [AC] (Voltage Output/Transformer Selection Table).
Use 18 AWG or larger for all power connections (Battery, DC output).
Keep power-limited wiring separate from non power-limited wiring
(115VAC / 60Hz Input, Battery Wires). Minimum 0.25" spacing must be provided.
CAUTION: Do not touch exposed metal parts. Shut branch circuit power before installing or
servicing equipment. There are no user serviceable parts inside.
Refer installation and servicing to qualified service personnel.
4. Measure output voltage before connecting devices. This helps avoiding potential damage.
5. Connect devices to be powered to terminals marked [– DC +].
6. When the use of stand-by batteries is desired, they must be lead acid or gel type. Connect battery to the
terminals marked [– BAT +] on the board (battery leads included). Use two (2) 12VDC batteries connected in
series for 24VDC operation.
Note: When batteries are not used, a loss of AC will result in the loss of output voltage.
SMP7
Power Supply/Charger
Installation Guide

Specifications:

Max. Load DC
SW1 ON
SW1 OFF

Installation Instructions:

Overview:

Battery Backup:
• Built-in charger for sealed lead acid or
gel type batteries.
• Maximum charge current 0.7A.
• Zero voltage drop when switching over
to battery backup.
Indicators:
• AC input and DC output LED indicators.
Board Dimensions (W x L x H approximate):
7" x 4.25" x 1.25"
(177.8mm x 107.9mm x 31.75mm).
Transformer Requirements
(Recommended Altronix Part #'s)
6A
24VAC or 28VAC / 175VA (T2428175)
6A
24VAC or 28VAC / 175VA (T2428175)

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the SMP7 and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

Summary of Contents for Altronix SMP7

  • Page 1 SMP7 should be installed in accordance with The National Electrical Code and all applicable Local Regulations. 1. Mount SMP7 in the desired location/enclosure (mounting hardware included). 2. Set SMP7 to the desired DC output voltage by setting the SW1 switch (Fig. 1a, pg. 2) to the appropriate position (Voltage Output/Transformer Selection Table).
  • Page 2 Stand-by battery connections. Maximum charge rate 0.7A. AC DC --- DC + Altronix is not responsible for any typographical errors. –––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––– 140 58th Street, Brooklyn, New York 11220 USA | phone: 718-567-8181 | fax: 718-567-9056 website: www.altronix.com | e-mail: info@altronix.com | Lifetime Warranty MEMBER IISMP7 - Rev.