Carrier REFRIGERANT R-410A Installation And Service Instructions Manual page 29

Packaged air-handling units 60 hz with puron (r-410a) refrigerant sizes 25, 28, 30
Hide thumbs Also See for REFRIGERANT R-410A:
Table of Contents

Advertisement

Table 9E — Medium-Static Drive Data, 60 Hz — SI
UNIT
MOTOR DRIVE
Motor Pulley Pitch Diameter (mm)
Pulley Factory Setting
Full Turns Open
FAN DRIVE
Pulley Pitch Dia (mm)
Pulley Bore (mm)
Belt No. — Section
Belt Pitch (mm)
FAN SPEEDS (r/s)
Factory Setting
Range
Max Allowable Speed (r/s)
1
Change per
/
Turn of
2
Moveable Motor Pulley
Flange
MAX FULL TURNS FROM
CLOSED POSITION
SHAFTS CENTER DISTANCE (mm)
Four belts shipped with unit. Use correct set of 2 belts sized according to the pully setting.
Table 9F — High-Static Drive Data, 60 Hz — SI
UNIT
MOTOR DRIVE
Motor Pulley Pitch Diameter (mm)
Pulley Factory Setting
Full Turns Open
FAN DRIVE
Pulley Pitch Dia (mm)
Pulley Bore (mm)
Belt No. — Section
Belt Pitch (mm)
FAN SPEEDS (r/s)
Factory Setting
Range
Max Allowable Speed (r/s)
1
Change per
/
Turn of
2
Moveable Motor Pulley
Flange
MAX FULL TURNS FROM
CLOSED POSITION
SHAFTS CENTER DISTANCE (mm)
It is possible to adjust drive so that fan speed exceeds maximum allowable. DO NOT exceed 20 r/s.
40RUA*25
40RUA*28
40RUS*25
40RUS*28
109.2-
109.2-
134.6
134.6
3.0
3.0
239
239
36.5
49.2
1—B
2—B
(2) 986
1062
(2) 1011
14.7
14.7
13.3-16.4
13.3-16.4
20.0
18.3
0.255
0.255
6
6
232-279
169-240
40RUA*25
40RUA*28
40RUS*25
40RUS*28
109.2-
109.2-
134.6
134.6
3.0
3.0
188
203
36.5
49.2
2—B
2—B
935
935
18.6
17.1
16.9-
14.6-
20.0
17.9
20.0
18.3
0.323
0.278
6
6
207-255
169-240
29
40RUA*30
40RUS830
109.2-
134.6
3.0
239
49.2
2—B
(2) 986
(2) 1011
14.7
13.3-16.4
18.3
0.255
6
169-240
40RUA*30
40RUS*30
109.2-
134.6
3.0
203
49.2
2—B
960
17.1
14.6-
17.9
18.3
0.278
6
169-240