Indoor Unit Only Operation - Mitsubishi Electric Ecodan EHSC-VM6D-CN Installation Manual

Hydrobox
Hide thumbs Also See for Ecodan EHSC-VM6D-CN:
Table of Contents

Advertisement

5
System Set Up
Outputs
Name
Terminal block Connector Item
OUT1
TBO.1 1-2
CNP1
OUT2
TBO.1 3-4
OUT6
CNBH 1-3
OUT7
CNBH 5-7
OUT11 TBO.3 5-6
OUT12 TBO.3 7-8
OUT15 TBO.4 1-2
OUT16 TBO.3 3-4
OUTA1 TBI.4 7-8
Do not connect to the terminals that are indicated as "—" in the "Terminal block" field.
N
L
N
L
TBO.3 5 6 7 8
TBO.1
1 2
3 4
OUT1
OUT2
Wiring specification and local supply parts
Item
Name
External output function
Outputs wire
Note:
1. When the hydrobox is powered via outdoor unit, the maximum grand total current of (a)+(b) is 3.0 A.
2. Do not connect multiple water circulation pumps directly to output (OUT1, OUT2). In such a case, connect them via (a) relay(s).
3. Do not connect water circulation pumps to both TBO.1 1-2 and CNP1 at the same time.
4. Stranded wire should be processed with insulation-covered bar terminal (DIN46228-4 standard compatible type).
5. Use the same thing as the Signal input wire for OUTA1 wiring.
5.3 Indoor unit only operation (during installation work)
In the case when heating operation is required prior to connection of the outdoor unit; i.e. during installation work, an electric heater in indoor unit (*1) can be used.
*1 Model with electric heater only.
1. To start operation
● Check if the indoor unit power supply is OFF, and turn DIP switch 4-4 and 4-5 ON.
● Turn ON the indoor unit power supply.
2. To end operation *2
● Turn OFF the indoor unit power supply.
● Turn DIP switch 4-4 and 4-5 OFF.
*2 When the indoor unit only operation is ended, ensure to check over the settings after outdoor unit is connected.
Note:
Prolonged running of the this operation may affect the life of the electric heater.
Water circulation pump 1 output
(Space heating)
Water circulation pump 2 output
(Space heating)
Booster heater 1 output
Booster heater 2 output
Error output
Defrost output
Comp ON signal
Thermo ON signal
Analog output
N L N L
N
L
TBI.4 8 7
TBO.4
1 2
OUT11 OUT12
OUT15
Model and specifications
Use sheathed vinyl coated cord or cable.
Max. 30 m
Wire type: CV, CVS or equivalent
Wire size: Stranded wire 0.25 mm² to 1.5 mm²
Solid wire: 0.25 mm² to 1.5 mm²
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
Normal
Error
Normal
Defrost
OFF
ON
OFF
ON
OUTA1
How to use TBO.1 to 4
Conductor
Outline view
Connect them using either way as shown above.
Signal/Max. current
220V AC 1.0A Max.
(Inrush current 40A Max.)
(a)
220V AC 1.0A Max.
(Inrush current 40A Max.)
220V AC 0.5A Max. (Relay)
220V AC 0.5A Max. (Relay)
220V AC 0.5A Max.
(b)
220V AC 0.5A Max.
220V AC 0.5A Max.
0-10V DC 5mA max.
Tool
Tool
Conductor
Top view
<Figure 5.2.2>
en
14