Carrier NP034-074 Installation, Start-Up And Service Instructions Manual page 12

Single package heating and cooling units
Hide thumbs Also See for NP034-074:
Table of Contents

Advertisement

WEIGHT
UNIT
SIZE
lb
kg
034
5400
2449
50DJ,DK,NP
044
6050
2744
J
UNIT
SIZE
mm
ft-in.
034
4168
13-8
50DJ,DK,NP
044
4999
16-4
Fig. 4B — Base Unit Dimensional Drawing; 50DJ,DK,NP034,044 Units
A
B
mm
ft-in.
mm
ft-in.
mm
4198
13-9
1
2916
9-6
13
6802
4
16
4948
16-2
13
3746
12-3
1
8015
16
2
K
CONN — Connection
mm
ft-in.
DIM
NOTES:
1
6321
20-8
7
16
8
1. Dimensions in [ ] are in millimeters.
13
7534
24-8
5
16
8
2.
3. Unit clearances:
Top — Do not restrict condenser fans
Control Box End — 6 -0
Sides — 6 -0
Economizer End — 6 -0 (except power exhaust units
10 -0 )
C
D
ft-in.
mm
ft-in.
mm
22-3
13
1711
5-7
3
2216
16
8
26-3
9
2247
7-4
7
2091
16
16
LEGEND
— Dimension
Center of Gravity includes economizer. Unit
weight does not include economizer.
12
E
F
G
ft-in.
mm
ft-in.
mm
ft-in.
7- 3
1
4428
9-0
1
3762
12-4
4
8
6-10
5
3363
11-0
3
4306
14-1
16
8
For smaller service and operational clearances, con-
tact Carrier Product Engineering Department.
4. Vertical discharge ducts designed to be attached to
accessory roof curb. If unit is mounted on dunnage,
support the ducts using cross braces as done on the
accessory roof curb.
5. When unit is slab mounted, locate the condensate
drain as low as possible on vertical face of base rail
at the same location as the standard condensate drain
(using factory supplied fitting). Plug factory drilled con-
densate hole.
H
mm
ft-in.
3
8
1
3769
12-4
3
2
8