Input Power and Control Wiring
Table 17. Drive terminal specifications
Frame Size
Cable Range
Frame 3 Drives (405, 600 A) (2) 1 - 500 KCM
Frame 4 Drives (900, 1200 A) (2) 1/0 - 750 KCM
Standard Control Wiring
WARNING
Hazardous Voltage with Improper
Grounding!
The motor controller has a chassis ground that MUST
be connected to an earth ground. You MUST follow
requirements for field wiring installation and grounding
as described in NEC and your local/state electrical
codes. Hazardous voltage due to improperly grounded
electrical components could result in death or serious
injury.
Table 18. CVHE, CVHF, & CVHG standard wiring requirements AFD control wiring (between the chiller and the starter)
AFD Starter to Control Panel Control
Wiring
AFD 120 volts ac Power Supply (hot)
AFD 120 volts ac Power Supply (neutral)
Ground
Oil Pump Interlock (2K11)
Condenser High Pressure Cutout (3S1)
Recomm Bus +24 V
Recomm Bus Ground
Recomm Bus Com +
Recomm Bus -
(a) Termination numbers may differ if the controls are CH531 or a Tracer AdaptiView™ controls upgrade.
Control wiring should be terminated at the terminal block
provided. The location of the control terminal block is
called out as item 13 on
Figure 1, p. 9
item 13 on
Figure 4, p. 13
p. 39
shows an expanded view of the terminal block
provided for control wiring. Field-installed control wiring
should be routed so that it is segregated from factory
installed wiring, unless the conductors of both circuits will
be insulated for the maximum voltage of either circuit.
38
Wire Binding 
Screw Torque
25 ft·lb (34 N·m)
25 ft·lb (34 N·m)
Starter Panel
Terminations
2X1-1
2X1-15
2X1-11
2X1-7, 2X1-8
2X1-3, 2X1-4
(shield to 2X1-5)
2A32-1
2A32-2
2A32-3
2A32-4
for Frame 3 units and
for Frame 4 units.
Figure 20,
Table 18
indicates the typical control wiring for AFDK
installation. Four knockouts have been provided on the left
side of the AFDK enclosure for control and communication
wires. For exact locations, refer to
Figure 8, p. 18
for Frame 3 units and refer to
and
Figure 10, p. 20
for Frame 4 units.
Control Panel
(a)
Terminations
1X1-1
1X1-12
1X1-18 or gnd
1A7 to J2-4, J2-2
NA
1A1-J4-1
1A1-J4-2
1A1-J4-3
1A1-J4-4
Figure 7, p. 17
and
Figure 9, p. 19
Comment
Panel ground.
Normally Open
Normally Closed. Operates the gate
kill input on 2A33
4-wire bus WB2 connects to power
supply module 1A1, terminals J4-1,
2, 3, and 4
AFDK-SVU01C-EN