Emerson COPELAND ZH04K1P Application Manuallines

Emerson COPELAND ZH04K1P Application Manuallines

Scroll compressors
Hide thumbs Also See for COPELAND ZH04K1P:
Table of Contents

Advertisement

Quick Links

Application Guidelines
Copeland
Scroll Compressors
for Heat Pump Applications with R410A
ZH04K1P to ZH19K1P
ZHI05K1P to ZHI46K1P

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the COPELAND ZH04K1P and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

Summary of Contents for Emerson COPELAND ZH04K1P

  • Page 1 Application Guidelines Copeland Scroll Compressors ™ for Heat Pump Applications with R410A ZH04K1P to ZH19K1P ZHI05K1P to ZHI46K1P...
  • Page 2: Table Of Contents

    About these guidelines .................... 1 Safety instructions ..................1 1.1 Icon explanation ....................1 1.2 Saf ety statements..................... 1 1.3 General instructions ..................2 Product description ..................3 2.1 Compressor range.................... 3 2.2 Nomenclature ....................3 2.3 Application range ..................... 4 2.3.1 Qualified refrigerants and oils ..............
  • Page 3 4.4.1 Internal line break motor protection ............21 4.4.2 External protection with Kriwan..............21 4.5 Kriwan protector f unctional check and failure detection..........22 4.5.1 Checking the connection ................22 4.5.2 Checking the compressor thermistor chain ..........22 4.5.3 Checking the protection module...............22 4.6 High-potential testing ..................23 Start-up &...
  • Page 4: About These Guidelines

    These application guidelines cover stationary applications only. For mobile ap plicat ions, p leas e contact the Application Engineering department at Emerson as other considerations may apply. Safety instructions Copeland scroll compressors are manufactured according to the latest European and US s af et y standards.
  • Page 5: General Instructions

    General instructions WARNING System breakdown! Personal injuries! Never install a system in t he f ield and leave it unattended when it has no charge, a holding charge, or with t he service valves closed without electrically locking out the system. System breakdown! Personal injuries! Only approved ref rigerants and ref rigeration oils must be used.
  • Page 6: Product Description

    Product description Compressor range These application guidelines deal with all vertical single Copeland scroll compressors for dedicated heat pump applications from ZH04K1P to ZH19K1P. They also cover vapour injection compressors f rom ZHI08K1P to ZHI46K1P. Heating Heating Compressor capacity Motor Compressor capacity Motor...
  • Page 7: Application Range

    5K is required. In the same way, the superheat at the compress or suction must always stay below a maximum limit specif ied by Emerson, depending on the model and for which the operating envelope is defined.
  • Page 8 This can be achieved by the use of wet vapour injection. For further information about wet vapour injec tion, c ontact A pplicat ion Engineering at Emerson. NOTE: For information and design recommendations regarding vapour injection, please refer to Technical Information C7.4.3 "Vapour injection scroll compressors for heat pumps".
  • Page 9: Dimensions

    Dimensions ZH04K1P, ZH05K1P ZH06K1P to ZH12K1P ZHI18K1P for tandem ZHI05K1P ZHI08K1P to ZHI23K1P ZHI23K1P for tandem ZH15K1P, ZH19K1P ZHI27K1P to ZHI32K1P ZHI35K1P, ZHI40K1P AGL_HP_ST_ZHK1P_EN_Rev00...
  • Page 10 ZHI46K1P AGL_HP_ST_ZHK1P_EN_Rev00...
  • Page 11: Installation

    The suction stub on compressor models ZHI27K1P to ZHI46K1P is located at low level. Oil might f low through the suction stub and get trapped in the syst em. To avoid t his, Emerson s trongly recommends mounting the suction piping turning vertically upward f rom the compressor connection.
  • Page 12: Mounting Parts

    For multiple compressor parallel configurations, the compressors must be positioned c ompletely vertically on a totally horizontal surface or rail. Mounting parts The compressors are designed to be mounted on vibration absorber grommets (part of the standard delivery). The grommets dampen the start-up surge of t he compressor and minimis e sound and vibration transmission to the compressor base during operat ion.
  • Page 13: Pressure Safety Controls

    The minimum cut-out setting shall be determined according to t he ref rigerant and t he allowed operation envelope – see Select software at www.climate.emerson.com/en-gb. AGL_HP_ST_ZHK1P_EN_Rev00...
  • Page 14: Crankcase Heaters

    This will prevent oil dilution and bearing stress on initial s tart -up. The crankcase heater must remain energized during compressor off cycles. NOTE: Please refer to the Spare Parts list available at www.climate.emerson.com/en- gb/tools-resources to select the correct crankcase heater model. Caution: Crankcase heaters must be properly grounded! For installation, the manufacturer/installer shall follow the recommendations mentioned below.
  • Page 15: Soft Starters

    However, f or extreme electrical conditions such as weak power supplies, single-phase soft starters can be supplied on request by Emerson, while three-phase sof t starters are available on the market. Discharge gas temperature protection...
  • Page 16 EXD TEVI (contact Emerson for more information). The controller has to stop the compressor when the maximum discharge gas temperature is exceeded.
  • Page 17: Excessive Discharge Gas Temperatures

    Since Copeland scroll compressors have a very high volumetric efficiency their displacements ar e lower than those of equivalent capacity reciprocating compressors. As a result, Emerson recommends that the capacity rating on reversing valves be no more than 1.5 to 2 times the nominal capacity of the compressor in order to ensure proper operat ion of t he rev ersing v alv e under all operating conditions.
  • Page 18: Sound And Vibration

    (two, three, or more) require additional oil balancing qualif ication between the parallel compressors. A sample compressor equipped with an external oil sight tube can be ordered from Emerson for lab testing. Records of the evaporating temperature and the bottom shell temperature s hall be t ak en wit h a high sampling rate during the entire oil return or oil balance testing and under all tested conditions.
  • Page 19: Suction Line Accumulator

    f ans or pumps cycling at low load and more. To evaluate the risk of liquid f loodbac k, p lease ref er to the oil dilution chart in Figure 16. Liquid level and superheat at compressor inlet have to be checked.
  • Page 20: Electrical Connection

    Electrical installation 4.2.1 Wiring diagrams The recommended wiring diagrams are shown in figures hereunder. NOTE: Emerson recommends using a contactor K2 for the safety chain in order to comply with EN 60335. Single-phase (PF*) compressors For the ZH04K1P to ZH12K1P and ZHI05K1P & ZHI11K1P ranges of compressors t he f ollowing...
  • Page 21 Three-phase compressors (TF*) with internal motor protection For the ZH04K1P to ZH19K1P and ZHI05K1P to ZHI40K1P ranges of compressors t he f ollowing circuit diagrams can be used: Power circuit Control circuit P> P< Motor terminal connections Three-phase compressors are connected to the T1, T2 and T3 connections Legend B1 ...
  • Page 22: Terminal Box

    Three-phase compressors (TWD) with external motor protection INT69SU2 For ZHI46K1P compressors the following circuit diagrams can be used: Power circuit Control circuit T1/L S1 S2 T2/N P> P< Motor terminal connections Three-phase compressors are connected to the T1, T2 and T3 connections Legend A1 ...
  • Page 23 Emerson advises installers/service providers to pay attention to this aspect every time they inst all or replace a Copeland scroll compressor and to use cable glands according to E N 50262 o r any other relevant standard of application in their country/region.
  • Page 24: Motor Winding

    4.2.3 Motor winding The ZH scroll compressors are offered with either a single-phase or a three-phase induction motor, depending on the size. All three-phase motors are connected in star; single-phase motors need a run capacitor. Motor insulation The motor insulation material is class "B" (PF* and TF*) or "H" (TW*) f or compressor models covered in these guidelines.
  • Page 25: Kriwan Protector Functional Check And Failure Detection

    115-230 V AC 50 Hz, -15 %...+10 %, 3 VA Supply voltage: Dual voltage 120-240 V AC 60 Hz, -15 %...+10 %, 3 VA 24 V AC 50/60 Hz, -15 %...+10 %, 3 VA Supply voltage 24 V DC  20 %, 2 W Ambient temperature range -30…+70 °C <...
  • Page 26: High-Potential Testing

    Emerson subjects all scroll compressors to a high-voltage test after final as sembly . E ach motor phase winding is tested, according to EN 0530 or VDE 0530 part 1, at a d if f erent ial voltage of 1000 V plus twice the nominal voltage.
  • Page 27: Start-Up & Operation

    DO NOT USE other industrial gases. 5.1.1 Compressor strength-pressure test The compressor has been strength-pressure tested in the Emerson factory . Theref ore, i t is not necessary for the system manufacturer/installer to strength-pressure test the compressor again.
  • Page 28: Preliminary Checks - Pre-Starting

    All compressors get a factory holding charge of dry air (about 1 to 2.5 bar, relativ e press ure). A n intact holding charge serves as a proof of quality against penetrating moisture. When removing plugs from the compressor, the plugs may pop out due t o p ressure and oil can spurt.
  • Page 29: Rotation Direction

    Rotation direction Scroll compressors, like several other types of compressors, will only compress in o ne rot ational direction. Direction of rotation is not an issue with single-phase compressors since they will always start and run in the proper direction. All three-phase compressors will ro tat e in eit her direct ion depending upon the phasing of the power.
  • Page 30: Pump-Out Cycle

    5.12 Minimum run time Emerson recommends a maximum of 10 starts per hour. There is no minimum of f t ime b ecause scroll compressors start unloaded, even if the system has unbalanced pressures. The most critical consideration is the minimum run time required to return oil to the compressor af t er s tart -up.
  • Page 31: Oil Level

    During the system development, adequate oil return in any operation should be checked what ever the compressor model. For this purpose, sample compressors equipped with sight t ubes can b e ordered from Emerson. Oil return check test recommendations are also available on demand f rom Application Engineering.
  • Page 32: Maintenance & Repair

    Maintenance & repair WARNING Conductor cables! Electrical shock! Follow the lockout/tag out proc edure and the national regulations before carrying out any maintenance or serv ic e work on the system. Use compressor with grounded system only. Screwed electrical connections must be used in all applications.
  • Page 33: Replacing A Compressor

    Co mpress ors s upplied b y Emerson contain oil with low moisture content, and it may ris e during t he s yst em as sembling process.
  • Page 34: Oil Additives

    (h=hours) Oil additives Although Emerson cannot comment on any specif ic product, f rom our own testing and past experience, we do not recommend the use of any additives to reduce compressor bearing los ses or f or any other purpose. Furthermore, the long term chemical stability of any additive in the...
  • Page 35: Troubleshooting

    Troubleshooting WARNING Electrical connections! Electrical shock hazard! Before at tempt ing any electrical troubleshooting, make sure all grounds are connected and s ecure and there is ground continuity throughout the compressor system. Also ensure the compressor system is correctly grounded to the power supply. If you are not a qualified service person familiar with electrical troubleshooting techniques, DO NOT PROCEED until a qualified service person is available.
  • Page 36 Condition Cause Corrective action Compressor Check if there is continuity on the compressor external motor protector. If the compressor is warm, it may require protector open considerable time to cool down. Def ective Check if the pressure control or thermostat works system control properly or if the controls are open.
  • Page 37 Too high Make sure the compressor operates within the compressor acceptable superheat range published by Emerson. superheat Excessive cooling/heating Check the load design; make sure that proper load or insulation is applied.
  • Page 38: Dismantling & Disposal

    The latest version of Copeland Select sof tware with perf ormance data and technical data is available from the webpage www.climate.emerson.com/en-gb. Spare parts and accessories: An online version of the Emerson spare parts and accessories s oft ware is av ailable f rom t he webpage www.climate.emerson.com/en-gb/tools-resources. DISCLAIMER 1.
  • Page 39 The Emerson logo is a trademark and service mark of Emerson Electric Co. Emerson Climate Technologies Inc. is a subsidiary of Emerson Electric Co. Copeland is a registered trademark and Copeland Scroll is a trademark of Emerson Climate Technologies Inc.. All other trademarks are property of their respective owners.

This manual is also suitable for:

Copeland zhi05k1p

Table of Contents