2.3

Application range

2.3.1 Qualified refrigerants and oils

Oil recharge values can be taken from Copeland scroll compressors brochures or Copeland Select
sof tware available at www.climate.emerson.com/en-gb.
Compressors
Qualified refrigerants
Copeland brand
products standard oil
Servicing oil
Table 2: Qualified refrigerant and oil

2.3.2 Application limits

CAUTION
Inadequate lubrication! Compressor breakdown! Copeland scroll
compressors are qualified for operation inside the envelope published by
Emerson. The envelope is def ined according to Emerson testing and
experience. Operating a compressor outside the envelope might lead to
compressor f ailure which would be the heat pump manuf acturer's
responsibility. The superheat at the compressor suction inlet must always be
suf ficient to ensure that no refrigerant droplets enter the compressor. For a
typical evaporator-expansion valve configuration a minimum stable superheat
of at least 5K is required. In the same way, the superheat at the compress or
suction must always stay below a maximum limit specif ied by Emerson,
depending on the model and for which the operating envelope is defined.
NOTE: The application envelopes shown below are for R410A.
ZH04K1P, ZH05K1P (up to S/N 15F)
75
70
65
60
55
50
45
40
35
30
25
20
15
10
-35 -30 -25 -20 -15 -10 -5
Evaporating Temperature (
Max 10K suction superheat
Max 10K suction superheat,
Max 5K suction superheat
Max 5K suction superheat,
4
ZH04K1P to ZH19K1P
ZHI05K1P to ZHI46K1P
Emkarate RL 32 3MAF
Emkarate RL 32 3MAF
R410A
0
5
10 15 20 25 30
o
C)
limited operation <2000 hours on a compressor lifetime
limited operation <2000 hours on a compressor life time
R410A
ZH04K1P, ZH05K1P (from S/N 15G onward s)
ZH06K1P to ZH19K1P (all S/N)
75
70
65
60
55
50
45
R410A
40
35
30
25
20
15
10
-35 -30 -25 -20 -15 -10 -5
Evaporating Temperature (
AGL_HP_ST_ZHK1P_EN_Rev00
0
5
10 15 20 25 30
o
C)