TEMP (F)
AIR ENT
COND
54
65
SPH
20.1
70
SPH
16.5
75
SPH
13.0
80
SPH
10.9
85
SPH
8.9
90
SPH
6.9
95
SPH
5.0
100
SPH
*
105
SPH
*
110
SPH
*
115
SPH
*
LEGEND
Ewb — Entering Wet Bulb
SPH — Superheat at Compressor (F)
SUPERHEAT
TEMP (F)
61.5
0
35
2
37
4
39
6
41
8
43
10
45
12
47
14
49
16
51
18
53
20
55
22
57
24
59
26
61
28
63
30
65
32
67
34
69
36
71
38
73
40
75
*Temperature at suction service valve.
Table 6F — Superheat Charging Table, 50SX060
56
58
60
20.1
20.1
20.1
16.5
16.5
16.5
13.0
13.0
13.0
10.9
10.9
10.9
8.9
8.9
8.9
6.9
6.9
6.9
5.0
5.0
5.0
*
*
*
*
*
*
*
*
*
*
*
*
*Do not attempt to charge system under these conditions — refrigerant slugging may occur.
Table 7 — Required Suction-Tube Temperature (F)*
SUCTION PRESSURE AT SERVICE PORT (psig)
64.2
67.1
37
39
39
41
41
43
43
45
45
47
47
49
49
51
51
53
53
55
55
57
57
59
59
61
61
63
63
65
65
67
67
69
69
71
71
73
73
75
75
77
77
79
EVAP AIR — CFM
1995
Evap Air — Ewb (F)
62
64
66
20.1
20.1
22.6
17.3
18.0
20.6
14.5
16.0
18.5
12.4
13.9
16.5
10.4
11.9
14.4
8.4
9.9
12.4
6.3
7.8
10.3
*
5.8
8.3
*
*
6.2
*
*
*
*
*
*
70.0
73.0
76.0
41
43
43
45
45
47
47
49
49
51
51
53
53
55
55
57
57
59
59
61
61
63
63
65
65
67
67
69
69
71
71
73
73
75
75
77
77
79
79
81
81
83
33
68
70
72
25.2
25.6
26.1
23.1
24.0
24.8
21.1
22.3
23.5
19.0
20.6
22.2
17.0
18.9
20.9
14.9
17.3
19.6
12.9
15.6
18.3
10.8
13.9
17.0
8.8
12.3
15.7
6.7
10.6
14.4
*
8.9
13.1
79.2
82.4
45
47
49
47
49
51
49
51
53
51
53
55
53
55
57
55
57
59
57
59
61
59
61
63
61
63
65
63
65
67
65
67
69
67
69
71
69
71
73
71
73
75
73
75
77
75
77
79
77
79
81
79
81
83
81
83
85
83
85
87
85
87
89
74
76
26.6
27.0
25.6
26.5
24.7
25.9
23.8
25.4
22.9
24.9
22.0
24.3
21.1
23.8
20.1
23.2
19.2
22.7
18.3
22.2
17.4
21.6
85.7
51
53
55
57
59
61
63
65
67
69
71
73
75
77
79
81
83
85
87
89
91

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents