Electrical Data - Carrier 50SS018-060 Installation, Start-Up And Service Instructions Manual

Single-package cooling units
Table of Contents

Advertisement

UNIT SIZE
V-PH-Hz
50SS
018
208/230-1-60
024
208/230-1-60
208/230-1-60
030
208/230-3-60
208/230-1-60
036
208/230-3-60
460-3-60
208/230-1-60
042
208/230-3-60
460-3-60
208/230-1-60†
208/230-1-60**
208/230-3-60†
048
208/230-3-60**
460-3-60†
460-3-60**
208/230-1-60†
208/230-1-60**
208/230-3-60†
060
208/230-3-60**
460-3-60†
460-3-60**
LEGEND
AWG
— American Wire Gage
BRKR — Breaker
CUL
— Canadian Underwriters' Laboratories
FLA
— Full Load Amps
HACR — Heating, Air Conditioning and
Refrigeration
LRA
— Locked Rotor Amps
MCA
— Minimum Circuit Amps
MOCP — Maximum Overcurrent Protection
NEC
— National Electrical Code
RLA
— Rated Load Amps
*Fuse or HACR Breaker.
†Carrier Scroll Compressor.
**Copeland Scroll Compressor.
NOTES:
1. In compliance with NEC requirements for multimotor and combi-
nation load equipment (refer to NEC Articles 430 and 440), the
overcurrent protective device for the unit shall be fuse or HACR
breaker. The CUL units may be fuse or circuit breaker.
2. Minimum wire size is based on 60 C copper wire. If other than
60 C wire is used, or if length exceeds wire length in table, de-
termine size from NEC.
3. Unbalanced 3-Phase Supply Voltage
Never operate a motor where a phase imbalance in supply volt-
age is greater than 2%. Use the following formula to determine
the percentage of voltage imbalance.
% Voltage Imbalance
max voltage deviation from average voltage
= 100 x
Table 4A — Electrical Data — 50SS Units
VOLTAGE RANGE
COMPRESSOR
Min
Max
RLA
187
253
8.3
187
253
12.4
187
253
14.4
187
253
9.4
187
253
18.0
187
253
11.7
414
506
5.6
187
253
20.4
187
253
14.0
414
506
6.4
187
253
21.8
187
253
26.4
187
253
12.8
187
253
15.0
414
506
16.0
414
506
19.3
187
253
28.9
187
253
32.1
187
253
6.4
187
253
8.2
414
506
8.0
414
506
10.0
average voltage
OUTDOOR-
INDOOR-
FAN
FAN
MOTOR
MOTOR
LRA
FLA
FLA
45.0
0.7
1.8
61.0
0.7
2.0
82.0
1.4
2.3
65.5
1.4
2.3
96.0
1.4
2.8
75.0
1.4
2.8
40.0
0.8
1.4
104.0
1.4
4.0
91.0
1.4
4.0
42.0
0.8
2.0
124.0
2.1
5.0
129.0
2.1
5.0
93.0
2.1
5.0
99.0
2.1
5.0
125.0
2.1
6.8
123.0
2.1
6.8
165.0
2.1
6.8
169.0
2.1
6.8
46.5
1.1
2.3
49.5
1.1
2.3
66.5
1.1
3.2
62.0
1.1
3.2
EXAMPLE: Supply voltage is 460-3-60.
Determine maximum deviation from average voltage.
(AB) 457 – 452 = 5 v
(BC) 464 – 457 = 7 v
(AC) 457 – 455 = 2 v
Maximum deviation is 7 v.
Determine percent of voltage imbalance.
% Voltage Imbalance = 100 x
This amount of phase imbalance is satisfactory as it is below the
maximum allowable 2%.
IMPORTANT: If the supply voltage phase imbalance is more than 2%,
contact your local electric utility company immediately.
22
AWG 60C
POWER SUPPLY
MIN WIRE
SIZE
MCA
MOCP*
12.0
15
14
18.2
30
12
21.8
30
10
15.5
25
12
26.7
40
10
18.8
30
12
9.2
10
14
30.9
50
8
22.9
35
10
10.8
15
14
40.1
60
6
40.1
60
6
23.1
35
10
25.9
40
10
33.0
40
8
33.0
50
8
49.0
60
6
49.0
60
6
11.4
15
14
13.7
20
14
16.8
20
12
16.8
25
12
AB = 452 v
BC = 464 v
AC = 455 v
452 + 464 + 455
Average Voltage =
3
1371
=
3
= 457
7
457
= 1.53%
MAX WIRE
LENGTH (ft)
75
80
100
80
90
65
100
100
85
100
100
100
75
75
90
90
100
100
100
100
100
100