Button Navigation Guide:
- Enters Advanced Menu, when held for 5 sec
Advanced
- Navigates between parameters
Menu
- Submits a modified parameter
- Goes up one level, when held for 5 sec
- Cancels a modified parameter, when held for 5 sec
13. Press the Menu button again the Unocc Heat Setpoint will
appear. The default setting is 62°F. To change the default, use the
arrow keys.
Screen timeout: 30 sec
14. Press the Menu button again the Unocc Cool Setpoint will
appear. The default setting is 78°F. To change the default, use the
arrow keys.
Screen timeout: 30 sec
15. Press the Menu button again and the Max Duct
Temp will appear if either 1 or 2 stage reheat or 0-10/2-10 volts
was enabled. The default setting is 80°F. To change the default
setting, use the arrow keys. This screen will be skipped if no
reheat is selected.
16. Press the Menu button again and the Max Duct Discharge
will appear if either 1 or 2 stage reheat or 0-10/2-10 volts was
enabled. The default setting is 120°F. To change the default
setting, use the arrow keys. This screen will be skipped if no
reheat is selected.
17. Press the Menu button again and the Slave Damper Enable
will appear. The default setting is Disable. To change the default,
use the arrow keys.
Screen timeout: 30 sec
18. Press the Menu button again and Motion Bypass will appear
if the TBN has a motion detector on board. The default setting is
Enable. To change the default setting, use the arrow keys.
19. Press the Menu button again and Motion Bypass Time will
appear if the TBN has a motion detector on board. The default
setting is 60 Minutes. To change the default setting, use the
arrow keys.
20. Press the Menu button again and CO
the TBN has CO
detection on board. The default setting is 800
2
ppm. To change the default setting, use the arrow keys.
Date: 12-2021
Supersedes: NEW
Nailor reserves the right to change any information concerning product or specification without notice or obligation.
TBN BACnet Thermostat • General Configuration
Setpoint will appear if
2
Page 5 of 6
- Modifies a parameter
- Goes up one level when pressed in Exit screen
- Releases an override when both are pressed
- Enters into a submenu
21. Press the Menu button again and Operation - Auto will
appear. This is the default for automatic damper operation.
Screen timeout: 30 sec
22. To use Hand Positions, press the UP arrow button until the
display reads Operation - Hand. This allows Hand Position to be
active.
If the UP arrow button is pressed again, the display will toggle
back to Auto. Press Menu to advance to next screen.
23. When in Hand Position, use the arrow buttons to increase or
decrease the damper position value. The default percentage is
25% which is the fixed position the damper will open.
Screen timeout: 30 sec
24. Exit the submenu via the arrow keys or let stat timeout.
and
OR
IOM-TBN