- Enters Advanced Menu, when held for 5 sec
Advanced
- Navigates between parameters
Menu
- Submits a modified parameter
- Goes up one level, when held for 5 sec
- Cancels a modified parameter, when held for 5 sec
Setting up the Network Parameters
From the TBN General Configuration submenu, the controller's
network parameters can be set.
How to enter the General Configuration submenu
To enter the General Configuration submenu:
1. Hold the Menu button for five seconds.
Screen timeout: none
The password field appears.
2. Use the arrow keys to increase or decrease the displayed
number until it matches the configured password.
Screen timeout: 15 sec
By default, the password is 9995.
3. Press the Menu button to submit the password.
Screen timeout: 15 sec
Upon submitting the correct password, the Advanced Menu is
entered and the Setpoints submenu is displayed.
4. Press the Menu button several times until GEN CFG appears
on the display.
Screen timeout: 15 sec
5. Press either of the arrow keys to enter the Configuration
submenu.
Screen timeout: 30 sec.
Upon entering the General Configuration submenu, the MAC
Address parameter appears.
Screen timeout: 30 sec
Date: 12-2021
Supersedes: NEW
Nailor reserves the right to change any information concerning product or specification without notice or obligation.
TBN BACnet Thermostat • Network Configuration
5 sec
- Modifies a parameter
- Goes up one level when pressed in Exit screen
- Releases an override when both are pressed
- Enters into a submenu
How to set up the BACnet® MS/TP
communication network parameters
The TBN can be used to set the controller's BACnet
and baud rate. In doing so, the TBN must have a subnet ID of 1.
To set up the network parameters:
1. Use the arrow keys to enter the controller's MAC address.
Screen timeout: 30 sec
2. Press the Menu button to submit the MAC address.
Screen timeout: 30 sec
The TBN subnet ID of 1 appears on the display.
3. Press the Menu button once to move onto the next parameter.
Screen timeout: 30 sec
The Baud Rate parameter appears on the display.
4. Use the arrow keys to set the baud rate.
Screen timeout: 30 sec
Keep in mind that all the devices on the data bus must be set to
the same baud rate. Typically, the baud rate is set at the router
level. Therefore, it is recommended to set the baud rate to AUTO
so that the baud rate being used on the data bus is automatically
detected and applied to the controller accordingly.
5. Press the Menu button to submit the baud rate.