- Enters Advanced Menu, when held for 5 sec
Advanced
- Navigates between parameters
Menu
- Submits a modified parameter
- Goes up one level, when held for 5 sec
- Cancels a modified parameter, when held for 5 sec
How to enter the Configuration submenu
To enter the Configuration submenu:
1. Hold the Menu button for five seconds.
Screen timeout: none
The password field appears.
2. Use the down arrow key to decrease the display number until
it matches the configured password.
Screen timeout: 15 sec
By default, the password is 9995.
3. Press the Menu button to submit the password.
Screen timeout: 15 sec
4. Once the password is accepted, press the Menu button again
and SETPOINT will appear on the screen.
Screen timeout: 30 sec
5. Press the up or down arrow key and the Bypass Time will
appear. The default setting is 60 minutes. To change the default
setting, use the arrow keys.
Screen timeout: 30 sec
6. Press the Menu button again and the Setpoint Low Limit will
appear. The default setting is 64°F. To change the default setting,
use the arrow keys.
Screen timeout: 30 sec
Date: 12-2021
Supersedes: NEW
Nailor reserves the right to change any information concerning product or specification without notice or obligation.
TBN BACnet Thermostat • General Configuration
Page 4 of 6
- Modifies a parameter
- Goes up one level when pressed in Exit screen
- Releases an override when both are pressed
- Enters into a submenu
7. Press the Menu button again and the Setpoint High Limit will
appear. The default setting is 74°F. To change the default setting,
use the arrow keys.
Screen timeout: 30 sec
8. Press the Menu button again an Reheat Config will appear. The
default setting is No Heat. To change the default setting, use the
arrow keys.
Screen timeout: 30 sec
9. Press the Menu button again and Min Position Heat will appear
only if 1 or 2 stage heating or 0-10/2-10 volts was selected on
the previous screen. The default setting is 10%. Use the arrow
keys to change the default setting. This screen will be skipped if
no reheat is selected and the next screen to appear will be Min
Damper Position.
Screen timeout: 30 sec
10. Press the Menu button again and the Minimum Damper
Position will appear. The default setting is 100%. To change the
default setting, use the arrow keys.
Screen timeout: 30 sec
11. Press the Menu button again and the Maximum Damper
Position will appear. The default setting is 100%. To change the
default setting, use the arrow keys.
Screen timeout: 30 sec
12. Press the Menu button again and the Unoccupied Damper
Position will appear. The default setting is 10%. To change the
default setting, use the arrow keys.