Commissioning, inspection, maintenance
Further details regarding the individual steps
Note
The nozzle pressures apply to 15 ºC,
1013 mbar, dry.
Checking the CO
Preparing the test
B
C
D
E
CO
test at the upper output
2
1. Press "+" E until the service display
has incremented to "00" (=100 %).
12
content
2
A
The gas pressure must not be altered
from these values because of the factory
setting to natural gas E or LL.
1. Open the gas shut-off valve.
2. Start the burner.
3. Press "S" D and "-" C simultane-
ously.
Display B will then show the follow-
ing:
■ Under status: "d" (= control stop)
■ Under service: Modulation level in
% ("00" = 100 % = upper output,
"00" = 0 % = lower output)
2. Check the CO
2
pipe.
(cont.)
content at the flue