Viessmann Vitoladens 300-W Installation And Service Instructions Manual page 54

Table of Contents

Advertisement

Code 2
General
(cont.)
Coding in the delivered condition
51:0
When there is a heat demand, the
internal circulation pump always
starts
52:0
Without flow temperature sensor
for low loss header
54:0
Without solar thermal system
6E:50
No correction of measured outside
temperature
76:0
Without LON communication mod-
ule
77:1
LON subscriber number
79:1
With LON communication module:
control unit is fault manager
7b:1
With LON communication module:
control unit transmits the time
7F:1
Detached house
80:6
A fault message is issued if a fault
is present for at least 30 s
54
Possible change
51:1
System with low loss header:
The internal circulation pump only
starts upon heat demand if the burn-
er is running.
The circulation pump stops on expiry
of the run-on time.
51:2
System with heating water buffer
cylinder:
The internal circulation pump only
starts upon heat demand if the burn-
er is running.
The circulation pump stops on expiry
of the run-on time.
52:1
With flow temperature sensor for low
loss header (automatic recognition)
54:1
With Vitosolic 100 (automatic recog-
nition)
54:2
With Vitosolic 200 (automatic recog-
nition)
54:3
With solar control module SM1 with-
out auxiliary function (automatic rec-
ognition)
54:4
With solar control module SM1 with
auxiliary function, e.g. central heat-
ing backup (automatic recognition)
6E:0
Outside temperature correction in
to
0.1 K steps
6E:100
0 to 49 = -5 K to -0.1 K
51 to 100 = 0.1 K to 5 K
76:1
With LON communication module
(automatic recognition)
77:2
LON subscriber number adjustable
to
from 1 to 99:
77:99
1 - 4 = Boiler
5 = Cascade
10 - 97 = Vitotronic 200-H
98 = Vitogate
99 = Vitocom
Note
Allocate each number only once.
79:0
Control unit is not fault manager
7b:0
No time transmission
7F:0
Apartment building
Holiday program and time program
for DHW heating can be set sepa-
rately
80:0
Immediate fault message
80:2
The minimum fault duration until a
to
fault message is issued is adjustable
80:199
from 10 to 995 s