Control unit

Heating mode

The control unit determines a set boiler water tempera-
ture subject to outside temperature or room tempera-
ture (if a room temperature-dependent remote control
is connected) and to the slope
curve.
The determined set boiler water temperature is trans-
ferred to the burner control unit. From the set and
actual boiler water temperatures, the burner control
unit calculates the modulation level and regulates the
burner accordingly.

Heating the DHW loading cylinder from cold

The heating circuit pump is switched ON and the 3-
way diverter valve will be changed over, if the cylinder
temperature sensor captures a temperature lower than
the defaulted set value.
The cylinder loading pump is switched ON if the
boiler water temperature
The burner is switched ON if the boiler water temper-
ature
set cylinder temperature, and the cylinder
loading pump is switched ON when the required
boiler water temperature is reached.

Reheating when DHW is drawn off

When DHW is drawn off, cold water enters the lower
section of the loading cylinder.
The heating circuit pump is switched ON and the 3-
way diverter valve is changed over, if the cylinder tem-
perature sensor captures a temperature lower than the
defaulted set value.
The cylinder loading pump is switched ON if the
boiler water temperature
The burner is switched ON if the boiler water temper-
ature
set cylinder temperature, and the cylinder
loading pump is switched ON when the required
boiler water temperature is reached.

Boosting DHW heating

This function is activated by specifying a second set
DHW temperature via parameter 58 in the "DHW"
group and activating the fourth DHW phase for DHW
heating.
level of the heating
/
set cylinder temperature.
set cylinder temperature.
The electronic temperature limiter inside the burner
control unit limits the boiler water temperature.
The loading cylinder is heated up to the set cylinder
temperature. Heating stops when the specified temper-
ature has been reached at the cylinder temperature
sensor.
DHW is regulated to the set temperature via the outlet
temperature sensor.
After the draw-off process has ended, the loading cyl-
inder continues to be heated up until the set DHW tem-
perature is reached at the cylinder temperature sensor.
Heating is boosted during the periods selected in this
time phase.