Drain Piping - LG A8UW54GFA0 Installation Manual

Hide thumbs Also See for A8UW54GFA0:
Table of Contents

Advertisement

Installation
!
CAUTION
Install certainly the decorative panel. Cool air leakage causes sweating. ⇨ Water drops fall.
Good example
Fit the insulator (this part) and
be careful for cool air leakage
HEAT INSULATION
1. Use the heat insulation material for the refrigerant piping which has an excellent heat-
resistance [over 120 °C(248 °F)].
2. Precautions in high humidity
circumstance:
This air conditioner has been tested
according to the "KS Standard
Conditions with Mist" and confirmed that
there is not any default. However, if it is
operated for a long time in high humid
atmosphere [dew point temperature:
more than 23 °C(73.4 °F)], water drops
are liable to fall. In this case, add heat
insulation material according to the
following procedure:
• Heat insulation material to be prepared... Adiabatic glass wool with thickness 10 to 20 mm.
• Stick glass wool on all air conditioners that are located in ceiling atmosphere.

Drain Piping

[Standard / Standard Libero / Artcool Mirror Type]
1. The drain hose should point downward for
optimum drainage.
2. Incorrect Installation Examples:
Do not raise
Water
leakage
26 Multi Air Conditioner
Air conditioner
unit
Ceiling
board
Decorative panel
Accumulated
drain water
Air
Water
Kinking
leakage
Bad example
Indoor unit
Tip of drain hose
dipped in water
Water
leakage
Ditch
Air conditioner unit
Air
Cool air leakage
(no good)
Ceiling
board
Decorative
panel
Fastening band
(accessory)
Refrigerant piping
Thermal insulator
(accessory)
Downward slope
Flexible drain hose
Less than 50 mm
(1 31/32 inch) gap