Ecm Interface Board & Thermostat Connections - Bosch DX Series Installation And Maintenance Manual

Table of Contents

Advertisement

14 Unitary Air Handler DX and Hydronic Series
6. Loosen the wheel set screw by placing wrench on
the screw head and turning counter clockwise.
Loosen the wheel set screw until the shaft can
spin freely 360° while inside the wheel hub. The
wheel set screw is located on the wheel hub on
the opposite side of the motor.
7. Remove the blower motor from the blower housing
by removing the screws on the sides of the housing
that secure the blower to the housing.
8. Remove the blower motor mount assembly by
loosening the belly band bolt and nut, then,
remove the belly bans and mount legs.
9. Insert the new blower motor into the blower
mounting bracket making sure the mounting
legs are properly placed into the belly band and
the legs are straight. Tighten the belly band
screw and nut until belly band is securely
fastened to the motor.
10. Place the motor into the housing so the mount
leg holes line up with the rivet nuts in the
housing. Place the screw into the mount leg
holes and tighten until the mount legs are
securely fastened to the housing.
11. Center the blower wheel in the housing, turn
the motor shaft so the wheel set screw is
located on the center of the flat spot of the
shaft and tighten the set screw.
12. Connect the same two cables that were
removed in step 3.
13. Slide the blower assembly into the blower deck,
replace the angle bracket, insert the screws
through the holes in the angle bracket and
tighten the screws into the holes in the blower
deck and the flanges in the casing.
14. Switch the circuit breakers to "ON" and replace
air handler blower door.
15. Turn on all electrical supply circuits to the furnace
at the main service (House Circuit Breaker) panel.
16. Set the thermostat to the desired temperature.
ECM INtERfACE bOARD AND
tHERMOStAt CONNECtIONS
The ECM Interface Board is used to connect the
thermostat wiring and the control wiring from the
remote condensing section or water-to-water unit.
6720220327
In addition to providing a connecting point for
thermostat wiring, the interface board also translates
thermostat inputs into control commands for the
variable speed programmable ECM DC fan motor and
displays an LED indication of operating status. The
thermostat connections and their functions are as
follows:
Y2
Y1
G
O
W1
EM/W2 Emergency Heat (electric heat only)
NC
C
R
HUM
If the unit is being connected to a thermostat with a
malfunction light, this connection is made at the
unit's malfunction output or relay.
Caution
Subject to change without prior notice
ECM Interface board
Second Stage Compressor Operation
First Stage Compressor Operation
Fan Operation
Reversing Valve (energized in cooling)
Auxiliary Electric Heat (runs in conjunction
with compressor)
Transformer 24 VAC Common (extra
connection)
Transformer 24 VAC Common (primary
connection)
Transformer 24 VAC Hot
Dehumidification Mode
If the thermostat is provided with a malfunction
light powered off of the common (C) side of the
transformer, the unit must be provided with a
malfunction relay (Bosch option # 660-006) to
properly energize the light. The relay coil will be
wired across the (ALR) and (C) contacts on the
unit's UPM board and the relay's normally open
contacts across (ALR) and the malfunction light
connection on the thermostat. If the thermostat is
provided with a malfunction light powered off of
the hot (R) side of the transformer, then the
thermostat malfunction light connection should be
connected directly to the (ALR) contact on the
unit's UPM board.
This only applies when the air handler is paired
with a Bosch condensing section. Other
condensing manufactures may have different type
of connections. Contact the manufacturer of the
condensing section for proper connection
methods when utilizing the malfunction light.
Revised 11-11

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents