Download Print this page

Emerson CASH VALVE B Installation Instruction

Pressure regulator

Advertisement

Quick Links

CASH VALVE™ TYPE B 1 ¼" - 2" PRESSURE REGULATOR
OXYGEN SERVICE INSTALLATION INSTRUCTION
Before installation, these instructions must be read carefully and understood.
WARNING
Failure to follow these instructions or to properly
install and maintain this equipment could result in
an explosion, fire and/or chemical contamination
causing property damage and personal injury or
death.
Cash Valve regulators must be installed, operated
and maintained in accordance with federal,
state and local codes, rules and regulations
and Emerson Process Management Regulator
Technologies, Inc. (Emerson) instructions.
If the regulator vents gas or a leak develops in
the system, service to the unit may be required.
Failure to correct trouble could result in a
hazardous condition. Installation, operation
and maintenance procedures performed by
unqualified personnel may result in improper
adjustment and unsafe operation. Either condition
may result in equipment damage or personal
injury. Only a qualified person shall install or
service the B Series regulator.
CALIFORNIA PROPOSITION 65 WARNING
This product can expose you to chemicals
including lead, which is known to the State of
California to cause cancer, birth defects, or other
reproductive harm. For more information, go to
www.P65Warnings.ca.gov.
INTRODUCTION
Scope of the Manual
This manual provides instructions for the
installation, adjustment, and maintenance for
the B Series pressure regulators.
Emerson.com
DESCRIPTION
The Type B pressure reducing and regulating
valve automatically reduces a high inlet
pressure to a lower delivery pressure and
maintains the lower pressure within reasonably
close limits regardless of the pressure
fluctuations on the inlet side of the valve.
SPECIFICATION DATA
Service: Oxygen gas (including medical
grade oxygen)
Sizes: 1 ¼, 1 ½ and 2" (32, 38 and 51 mm)
Connections: Threaded internal inlet and outlet
Body Material: Bronze
Temperature Rating: +150 to -320°F
(65.6 to -195.6°C)
Maximum Initial Pressure: 400 psi (27.58 bar)
Capacity: For specific capacity information,
consult the factory.
GENERAL INSTALLATION INSTRUCTIONS
The Type B regulator should be installed in the
horizontal position with the spring chamber
upright. For other installation requirements,
consult the factory. For easy operation and
maintenance, it is suggested that manual
shut-off valves be installed upstream and
downstream from the valve. Before installing
the valve, all piping should be thoroughly
flushed out to remove any foreign material.
Install the valve with the inlet pipe fitted to
the inlet connection identified on the valve
body. Use a compatible sealant on the male
pipe threads and do not over tighten the
valve connections.
© 2018 Emerson. All rights reserved.
CONSTRUCTION
Bronze body, brass internal trim, Buna-N
diaphragms and seat, Stainless steel
pressure spring.
All parts are commercially cleaned for
oxygen service.
OPERATING INSTRUCTIONS
Adjusting the Delivery Pressure
The regulator's delivery pressure setting is
adjusted by turning the Adjusting Screw (2) or
optional T-Handle (1) at the top of the Spring
Chamber (5) after loosening the Adjusting
Screw Lock Nut (3). To increase the delivery
pressure, turn the adjusting screw clockwise
(into the spring chamber). To decrease the
delivery pressure, turn the adjusting screw
counter-clockwise (out of the spring chamber).
Tighten the adjusting screw lock nut after the
adjustment has been made.
MAINTENANCE INSTRUCTIONS
CAUTION
Before attempting to replace any spare parts, be
sure to shut off all pressure connections to the
valve. With the valve closed, the system pressure
could still be locked between the shut-off valve
and the inlet and/or outlet sides of the regulator.
Before proceeding with any valve service, be
certain to relieve the pressure from both sides of
the regulator.
Refer to section view for parts identification.
Repair parts can easily be installed without
removing the regulator from the line.
VCIOM-10800-EN 22/01

Advertisement

loading

Summary of Contents for Emerson CASH VALVE B

  • Page 1 Use a compatible sealant on the male pipe threads and do not over tighten the Refer to section view for parts identification. valve connections. Repair parts can easily be installed without removing the regulator from the line. Emerson.com VCIOM-10800-EN 22/01 © 2018 Emerson. All rights reserved.
  • Page 2 VCIOM-10800 © 2018, 2022 Emerson Electric Co. All rights reserved 01/22. Cash Valve is a mark owned by one of the companies in the Emerson Automation Solutions business unit of Emerson Electric Co. The Emerson logo is a trademark and service mark of Emerson Electric Co. All other marks are the property of their prospective owners.