2) Edit the settings of the new Generic Ethernet Module. As shown in the screen shot
below, the module was named "HD67D25" and the IP-address assigned is 192.168.0.5.
For the Comm Format "Data – SINT" shall be selected as the data type.
RSLogix 5000 requires a configuration assembly instance. Both modules do not provide a
configuration assembly instance. Therefore it is allowed to select an instance of 3 and to
set the value to zero.
3) The setting of 10msec for the "Requested Packet Interval (RPI)" is adequate but it
is possible to change this value as required. A lower value of 2ms shall not be selected.
Warning:
The field "Use Unicast Connection over EtherNet/IP" must be checked.