Series EC-11 and EC-14 Sprinklers,
11.2 K and 14.0 K Upright and Pendent
Extended Coverage Light and Ordinary Hazard
General
Description
TYCO
Series
EC-11
and
Extended
Coverage
Upright
Pendent Sprinklers are decorative
glass-bulb sprinklers designed for
use in light or ordinary hazard occu-
pancies. They are intended for use in
automatic sprinkler systems designed
in accordance with standard installa-
tion rules (e.g., NFPA 13) for a maximum
coverage area of 400 ft
(37,2 m
2
compared to the maximum coverage
area of 130 ft
(12,1 m
) for standard
2
2
coverage sprinklers used in ordinary
hazard occupancies or 225 ft
for standard coverage sprinklers used
in light hazard occupancies.
Series EC-11 and EC-14 Sprinklers
feature a UL and C-UL Listing that
permits their use with unobstructed
or non-combustible obstructed ceiling
construction as defined and permitted
by NFPA 13, as well as a specific appli-
cation listing for use under concrete
tees.
Series EC-11 and EC-14 Extended
Coverage Sprinklers have been fire
tested to compare their performance to
that of standard coverage spray sprin-
klers. These tests have shown that the
protection provided is equal to or more
effective than standard coverage spray
sprinklers.
IMPORTANT
Always refer to Technical Data
Sheet TFP700 for the "INSTALLER
WARNING" that provides cautions
with respect to handling and instal-
lation of sprinkler systems and
components. Improper handling and
Installation can permanently damage
a sprinkler system or its compo-
nents and cause the sprinkler to fail
to operate in a fire situation or cause
it to operate prematurely.
Page 1 of 8
Corrosion-resistant coatings, where
applicable, help extend the life of
copper alloy sprinklers beyond that
which occurs when exposed to
corrosive atmospheres. Although corro-
EC-14
sion-resistant coated sprinklers passed
and
standard corrosion tests of the appli-
cable approval agencies, this testing
is not representative of all possible
corrosive atmospheres. Consequently,
it is recommended that the end user be
consulted with respect to the suitability
of these corrosion-resistant coatings
for any given corrosive environment.
), as
2
The effects of ambient temperature,
concentration of chemicals, and gas/
chemical velocity should be consid-
ered, along with the corrosive nature of
(20,6 m
)
2
2
the chemical to which the sprinklers will
be exposed.
NOTICE
Series EC-11 and EC-14 Extended
Coverage Sprinklers described herein
must be installed and maintained in
compliance with this document, as well
as with the applicable standards of the
National Fire Protection Association, in
addition to the standards of any other
authorities having jurisdiction. Failure to
do so may impair the performance of
these devices.
The owner is responsible for main-
taining their fire protection system and
devices in proper operating condition.
Contact
the
or product manufacturer with any
questions.
NOVEMBER 2014
installing
contractor
Sprinkler
Identification
Numbers (SINs)
TY5137 - Upright, 11.2K
TY5237 - Pendent, 11.2K
TY6137 - Upright, 14.0K
TY6237 - Pendent, 14.0K
TY5137 is a re-designation for C5137,
G1894, and S2510.
TY5237 is a re-designation for C5237,
G1893, and S2511.
TY6137 is a re-designation for C6137,
G1896, and S2610.
TY6237 is a re-designation for C6237,
G1895, and S2611.
TFP220

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the EC-11 Series and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

Summary of Contents for Tyco EC-11 Series

  • Page 1 Extended Coverage Light and Ordinary Hazard General Corrosion-resistant coatings, where applicable, help extend the life of Description copper alloy sprinklers beyond that which occurs when exposed to corrosive atmospheres. Although corro- TYCO Series EC-11 EC-14 sion-resistant coated sprinklers passed Extended Coverage Upright...
  • Page 2 When 3/4 inch NPT the rated temperature is reached, the Approvals fluid expands sufficiently to shatter Discharge Coefficients TYCO Series EC-11 EC-14 the glass bulb, which then allows the K = 11.2 gpm/psi (161,3 lpm/bar Extended Coverage Upright, Pendent, sprinkler to activate and flow water.
  • Page 3 TFP220 Page 3 of 8 Sprinkler Finish (See Note 5) Bulb Hazard Type Temperature Liquid Natural Chrome Lead Polyester* Brass Plated Coated 135°F (57°C) Orange 1, 2, 3**, 4 Upright 155°F (68°C) K=11.2 (TY5137) Light 175°F (79°C) Yellow Pendent K=11.2 (TY5237) 200°F (93°C) Green 1, 2, 4...
  • Page 4 TFP220 Page 4 of 8 HC-1 Linear Spacing Area Spacing Ceiling Ceiling Type K-factor Style Response Height Noncombustible Unobstructed, 11.2 EC Pendent or Up to 30 Noncombustible Obstructed, or 14.0 EC Upright Combustible Unobstructed Noncombustible Unobstructed, Pendent 11.2 EC Up to 30 Noncombustible Obstructed, or Recessed 14.0 EC...
  • Page 5 TFP220 Page 5 of 8 Group I Group II Light Hazard Ordinary Hazard Ordinary Hazard 0.10 gpm/ft Description Area 0.15 gpm/ft 0.20 gpm/ft 14 x 14 12.1 16 x 16 12.1 20.7 TY5137 (K=11.2) Upright 18 x 18 19.1 33.7 20 x 20 12.8 28.7...
  • Page 6 TFP220 Page 6 of 8 2-7/8" DIA. 2-7/8" DIA. (73,0 mm) 1/2" (12,7 mm) (73,0 mm) 3/4" (19,1 mm) 1/2±1/8" 5/8±1/4" (12,7±3,2 mm) (15,9±6,4 mm) 1/4" (6,4 mm) 1/4" (6,4 mm) 2-1/4" DIA. 2-1/4" DIA. (57,2 mm) (57,2 mm) FACE OF FACE OF 1/8"...
  • Page 7 For warranty terms and conditions, visit replaced. Also, replace any sprinkler www.tyco-fire.com. Apply the wrench recess of the appli- that has a cracked bulb or that has lost cable sprinkler wrench (Figure 5 and 6) liquid from its bulb.
  • Page 8 TFP220 Page 8 of 8...