Tyco EC-11 Series Manual

Tyco EC-11 Series Manual

11.2 and 14.0 k-factor extended coverage (light and ordinary hazard) upright, pendent, and rec.pendent sprinklers

Advertisement

Quick Links

Series EC-11 & EC-14 — 11.2 and 14.0 K-factor Extended
Coverage (Light and Ordinary Hazard) Upright, Pendent,
and Rec.Pendent Sprinklers
General
Description
The Series EC-11 and EC-14 Extended Cov-
erage Upright and Pendent Sprinklers are
decorative glass bulb sprinklers designed
for use in light or ordinary hazard occupan-
cies. They are intended for use in automatic
sprinkler systems designed in accordance
with standard installation rules (e.g., NFPA
13) for a maximum coverage area of 400 ft2
(37,2 m2), as compared to the maximum
coverage area of 130 ft2 (12,1 m2) for stan-
dard coverage sprinklers used in ordinary
hazard occupancies or 225 ft2 (20,6 m2) for
standard coverage sprinklers used in light
hazard occupancies.
The Series EC-11 and EC-14 Sprinklers fea-
ture a UL and C-UL Listing that permits their
use with unobstructed or non-combustible
obstructed ceiling construction as defined
and permitted by NFPA 13, as well as a spe-
cific application listing for use under con-
crete tees.
The Series EC-11 and EC-14 Extended Cov-
erage Sprinklers have been fire tested to
compare their performance to that of stan-
dard coverage spray sprinklers. These tests
have shown that the protection provided
is equal to or more effective than standard
coverage spray sprinklers.
IMPORTANT
Always refer to Technical Data Sheet
TFP700 for the "INSTALLER WARNING"
that provides cautions with respect to
handling and installation of sprinkler
systems and components. Improper han-
dling and installation can permanently
damage a sprinkler system or its compo-
nents and cause the sprinkler to fail to
operate in a fire situation or cause it to
operate prematurely.
Page 1 of 8    
http://www.tyco-fireproducts.com
Corrosion resistant coatings, where ap-
plicable, are utilized to extend the life of
copper alloy sprinklers beyond that which
would otherwise be obtained when ex-
posed to corrosive atmospheres. Although
corrosion resistant coated sprinklers have
passed the standard corrosion tests of the
applicable approval agencies, the testing is
not representative of all possible corrosive
atmospheres. Consequently, it is recom-
mended that the end user be consulted
with respect to the suitability of these cor-
rosion resistant coatings for any given cor-
rosive environment. The effects of ambient
temperature, concentration of chemicals,
and gas/chemical velocity, should be con-
sidered, as a minimum, along with the cor-
rosive nature of the chemical to which the
sprinklers will be exposed.
The Series EC-11 and EC-14 Extended Cover-
age Sprinklers described herein must be in-
stalled and maintained in compliance with
this document, as well as with the applicable
standards of the National Fire Protection As-
sociation, in addition to the standards of any
other authorities having jurisdiction. Failure
to do so may impair the performance of
these devices.
The owner is responsible for maintaining their
fire protection system and devices in proper
operating condition. The installing contrac-
tor or sprinkler manufacturer should be con-
tacted with any questions.
 
 
 
    February, 2007 
WARNINGS
Model/Sprinkler
Identification
Number
TY5137 - Upright, 11.2K
TY5237 - Pendent, 11.2K
TY6137 - Upright, 14.0K
TY6237 - Pendent,14.0K
TY5137 is a redesignation for C5137,
G1894, and S2510.
TY5237 is a redesignation for C5237,
G1893, and S2511.
TY6137 is a redesignation for C6137,
G1896, and S2610.
TY6237 is a redesignation for C6237,
G1895, and S2611.
TFP220_EN

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the EC-11 Series and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

Summary of Contents for Tyco EC-11 Series

  • Page 1 Series EC-11 & EC-14 — 11.2 and 14.0 K-factor Extended Coverage (Light and Ordinary Hazard) Upright, Pendent, and Rec.Pendent Sprinklers General Corrosion resistant coatings, where ap- plicable, are utilized to extend the life of copper alloy sprinklers beyond that which...
  • Page 2 Page 2  of 8  TFP220_EN 3/4” ** WRENCH ESCUTCHEON PLATE FLAT SEATING SURFACE 1 - Frame 2 - Button 3 - Sealing Assembly 4 - Bulb 5 - Compression Screw 6 - Deflector* 2-7/16” (61,9mm) * Temperature rating is UPRIGHT & indicated on deflector PENDENT ** Pipe thread connections per ISO...
  • Page 3 TFP220_EN   Page 3 of 8 LIGHTHAZARD ORDINARY HAZARD 57°C 68°C 79°C 93°C 141°C 57°C 68°C 79°C 93°C 141°C AREA STYLE 14 x 14 Up. or Pend. — — — — — 14 x 14 Style 30 Recessed — — — — — 14 x 14 Style 40 Recessed —...
  • Page 4 Page 4  of 8  TFP220_EN Technical Design obstructions to sprinkler discharge, obstruc- tions to sprinkler pattern development, Data Criteria obstructions to prevent sprinkler discharge from reaching hazard, clearance to storage, etc. Approvals The Series EC-11 and EC-14 Extended Cov- erage Sprinklers must only be installed in UL and C-UL Listed.
  • Page 5 TFP220_EN   Page 5 of 8 2-7/8” DIA. “FITTING SIDE” 1/2” (12,7 mm) (73,0 mm) 1/2±1/8” TOWARDS SPRINKLER FITTING (12,7±3,2 mm) 1/4” (6,4 mm) 2-1/4” DIA. (57,2 mm) FACE OF 1/8” SPRINKLER (3,2 mm) FITTING WRENCH RECESS (END “A”) MOUNTING MOUNTING FIGURE 4 SURFACE PLATE W-TYPE 3 SPRINKLER WRENCH...
  • Page 6 Page 6  of 8  TFP220_EN GROUP I GROUP II LIGHT HAZARD ORDINARY HAZARD ORDINARY HAZARD 0.10 GPM/FT2 0.15 GPM/FT2 0.20 GPM/FT2 DESCRIPTION AREA TY5137 (K=11.2) UPRIGHT 14 x 14 — — 12.1 16 x 16 12.1 20.7 18 x 18 19.1 33.7 20 x 20 12.8 28.7 51.0 TY5237 (K=11.2) PENDENT 14 x 14 — —...
  • Page 7 Maintenance protection system and devices in compli- Products manufactured by Tyco Fire & Build- ance with this document, as well as with ing Products (TFBP) are warranted solely to the applicable standards of the National...
  • Page 8 English version of document TFP220 which is the official version of the document. Any discrepancies or differences created in the translation are not binding and have no legal effect for compliance, enforcement or any other purposes. www.quicksilvertranslate.com. TYCO FIRE PRODUCTS, 451 North Cannon Avenue, Lansdale, Pennsylvania 19446 TYCO FIRE & BUILDING PRODUCTS, 451 North Cannon Avenue, Lansdale, Pennsylvania 19446...

This manual is also suitable for:

Ec-14 seriesTy5137Ty5237Ty6137Ty6237

Table of Contents