Components scheme of external device of the heat pump LINE KITA Mi Templari® 14 Components scheme of external device of the heat pump LINE KITA L Templari® .. 15 Components scheme of external device of the heat pump KITA Li Plus Templari® . 16 Trasport ........................
Page 3
11.6 Wiring diagram KITA S 3Ph / S 3Ph Plus ..............38 11.7 Wiring diagram KITA Si / Si Cold / Si Plus / Si Plus Cold / Mi / Mi Cold / Mi Plus / Mi Plus Cold mono-phase ..................39 11.8 Wiring diagram KITA Si 3Ph / Si Cold 3Ph / Si Plus 3Ph / Si Plus Cold 3Ph /Mi 3Ph /...
Page 4
HCC connection ....................46 14.1 Exploded view: Plan connection (5a) or BMS connection (5b) ....... 47 Control terminal ....................50 15.1 Fixing of the panel ....................50 15.2 Measures of unit command .................. 50 15.3 Menu overview ....................51 15.4 Terminal buttons ....................52 15.5 Display of the terminal ..................52 15.6 Main menu ......................
KITA • Scissors; Templari®, from its put in action during its whole life cycle . The • Set of wrenches or pipe wrench; document is divided in chapters, in each of them there are general •...
Read carefully before use Proper use The heat pump KITA Templari® is homologate just for the use 2.1 Important information providede by the manufacturer. A different use moving away WARNINGS! from the provided one is considered not-compliant. The proper use also includes the respect of the information included in The practice and the maintenance of the heat pump KITA the relevant informative.
40°C. Heat pump The KITA Templari® heat pump is equipped with a safety pressure switch, which interrupts the operation of the machine when a pressure of 4.5 MPa (45 bar) is reached. The product is equipped with a volume flow sensor (flow meter).
3.2.2 KITA with Scroll Vapor Injection Components KITA Si - Si 3Phase - Si Cold - Si Cold 3Phase KITA S - S 3phase - S plus - S plus 3phase - - Si Plus - Si Plus 3Phase - Si Plus Cold - Si...
KITA Mi plus - Mi plus 3phase - Mi plus Cold - Components Mi plus Cold 3phase - L33: circulator Wilo KITA L42, L66 Para 25/9 iPWM Model Grundfos UPMXL GEO 25-125 180 Model Wilo Para 25/9 iPWM Voltage - supply frequency...
Δp-c max. Compressor Equipment of supply Main unit Q/m³/h The heat pump KITA Templari® is supplied in two units and it is composed by the components showed in figure 1. 3.7 Mode of operation 4.2 Model name and registration number The heat pump can work in two ways, achievable through the...
Page 12
Templari srl Via Pitagora 20/A 35030 Rubano - PD info@templari.com +39 049 5225929 Wärmepumpe / Heat pump/Chiller / Pompa di calore Model / Model / Modello KITA M SPLIT Baujahr / time of production / Anno di fabbricazione 2020 Wärmeleistung / Heating Capacity / Potenza nominale...
Components scheme of external device of the heat pump KITA S/Si Templari® RELEASE VALVES ELECTRIC BOARD EVAPORATOR PLATE HEAT EXCHANGER COMPRESSOR CIRCULATION PUMP FILTER ECONOMIZER FLOWMETER CHECK VALVES LIQUID INDICATOR ELECTRONIC EXPANSION VALVE INVERTER 4-WAY VALVE LIQUID RECEIVER The image is intended only to indicate the main internal components. The actual product may looks different.
Bottom view The transport to the final place of installation should be done 1406 on a pallelt. The heat pump KITA Templari® can be transported using a forklift. KITA S LINE Kg. 180 KITA M LINE Kg.
DETTAGLIO CONNESSIONI sufficient air flow and facilitate maintenance works. • Verify there is asufficient space for the installation of the A water inlet / ingresso acqua TEMPLARI SRL - hydraulic piping. Via Pitagora, 20 connec�on / raccordo : 1" 1/2 Tel.
• Preparation of the base for condensate drain Preparation of the condensate drain The condensate is discharged in a centralized way from the back of the heat pump KITA Templari®. Prepare the condensate drain through a drain pipe or a gravel bed. WARNINGS! The condensate frozen on the avenues can cause falls. Verify that the condensate doesn’t flow on the avenues and can’t freeze on...
Alignment of the heat pump KITA Templari® Put horizontally the heat pump KITA Templari® so that the condensate can flow. The product must be installed with amortized feet, purchased separately. The amortized feet increase the height of the product, facilitating the flow of condensate and reducing vibrations.
• The installation of a Y filter is necessary. WARNINGS! Install hydraulic system side a safety valve. 7.3 Installation of hydraulic part • Thorough washing of the system with clean water filling and emptying it many times.
7.5 Diagram 1: cooling/heating system with buffer tank Anti-vibration joint SIGNAL CABLES Buffer tank temperature probe Manometer DHW temperature probe Drin tap Outlet temperature probe 3 way valve Inlet temperature probe Expansion vessel Y-filter External unit Bypass valve USER INTERFACE COLLECTOR WARNINGS! The buffer tank must comply with a minimum quantity of litres according to the heat pump Kita used: KITA S 200 Litres, KITA M 300...
7.6 Diagram 2: cooling/heating system with buffer tank and secondary buffer tank with DHW instant heater Anti-vibration joint SIGNAL CABLES Buffer tank temperature probe Manometer DHW temperature probe Drin tap Outlet temperature probe 3 way valve Inlet temperature probe Expansion vessel Y-filter External unit Bypass valve USER INTERFACE COLLECTOR WARNINGS! The buffer tank must comply with a minimum quantity of litres according to the heat pump Kita used: KITA S 200 Litres, KITA M 300 Litres, KITA L 500 Litres, KITA Li Plus 800 Litres.
7.7 Diagram 3: cooling/heating system with buffer tank and technical water buffer tank with coil for instant DHW production Anti-vibration joint SIGNAL CABLES Buffer tank temperature probe Manometer DHW temperature probe Drin tap Outlet temperature probe 3 way valve Inlet temperature probe Expansion vessel Y-filter External unit Bypass valve USER COLLECTOR INTERFACE WARNINGS! The buffer tank must comply with a minimum quantity of litres according to the heat pump Kita used: KITA S 200 Litres, KITA M 300...
7.8 Diagram 4: “T” cooling/heating system with buffer tank, DHW storage tank and Controlled Mechanical Ventilation Anti-vibration joint SIGNAL CABLES Buffer tank temperature probe Manometer DHW temperature probe Drin tap Outlet temperature probe 3 way valve Inlet temperature probe Expansion vessel Y-filter External unit Bypass valve CONTROLLED MECHANICAL VENTILATION COLLECTOR FLOOR ROOM...
Maintenance and cleaning Cleaning of the condensate drain Make sure that the condensate drainpipe is in the correct position A periodic maintenance is necessary first of all to keep a correct and no clogged, to allow the correct drain of the condensate and efficient operation of the heat pump, in order to reduce depositing on the battery during the operation in the heat pump.
5,58 1,99 2,80 30mA 3x2,5 KITA Si Plus 6,31 1,75 3,60 30mA KITA Si Cold 9,10 1,77 5,14 30mA KITA Si Plus Cold 10,70 1,50 7,10 30mA 230V/1ph KITA Mi 7,80 1,69 4,60 30mA KITA Mi Cold 11,80 1,47 8,00...
10 Terminal wiring 10.1 Terminal wiring outdoor unit The following scheme is valid for all Kita Split model: Version 1 - No optional accessories Connector description Subcooling RX-/TX- Radiant probe +Vdc RX+/TX+ Domestic probe Return probe +5 Vref Flow meter Head compressor probe Vout Flow probe...
Page 30
Version 2 - A relè to manage DHW or auxiliary For standard connections make reference to the table mentioned in version 1. Here below is shown the table with the contacts for integration. the connection of the relé K3...
Page 31
A1 K3 NO6 µPC A2 K3 Neutral external unit 11 K3 S/L Phase* external unit *S 3-phase version, L monophase version Relè K3 INTEGRATION MANAGEMENT Relay coil to NO6 uPC contact Relay coil to Neutral external unit Normally open contact (NO)
Page 32
Version 3 - Two relay, to manage DHW and Make reference to the table in paragraph 12.2 of the complete manual for standard connections. auxiliary integration Here below is shown the table with the contacts for the connection of relès K1 and K3.
Page 33
Normally open contact (NO) Normally open contact (NO) Normally closed contact (NC) Normally closed contact (NC) Common contact (C) Common contact (C) Connection 3-way valve Templari - de pala OUT DHW and integration 3-WAY VALVE K1 RELAY EXTERNAL UNIT Phase open (BROWN)
10.2 Plant Aware Function The PA function can be enabled using the HCC panel from the mask “More”. Available from software version 13.69.001 of 07/10/2020 In this case there is at least one ROOM sensor or a cMix board. The HCC PA system function overwrites and replaces the PA The Plant Aware function (PA) modifies the hysteresis for the settings of the heat pump.
10.3 Wiring pLAN net - “multi-KITA” If more unit KITA Templari® are connected each other it is possible to make them interact by a pLAN “multi-KITA” logic; it is possible to connect 4 units in cascade at last. It is necessary to connect the machines through a bipolar cable...
11 Electronic board KITA S - S 3phase - S plus - S plus 3phase - Si - Si 3Phase - Si Cold - Si Cold 3Phase - Si Plus - Si Plus 3Phase - Si Plus Cold - Si...
11.8 Wiring diagram KITA Si 3Ph / Si Cold 3Ph / Si Plus 3Ph / Si Plus Cold 3Ph /Mi 3Ph / Mi Cold 3Ph / Mi Plus 3Ph / Mi Plus Cold 3Ph / L33 / L42 Flowmeter...
11.10 Internal wiring connection diagram 11.10.1 Circulation pump Yellow/Green Yellow/Green Yellow/Green Yellow/Green Blue Blue Blue Blue Brown Brown Brown Brown N-Lok 3 N-Lok 3 N-Lok 3 N-Lok 3 11.10.2 Fan Brown Brown Brown Brown Brown Brown Brown Brown Yellow/Green Yellow/Green Yellow/Green Yellow/Green Blue Blue...
12 Initial operation The start up of the system has to be made by a competent staff that received a specific training. After the correct hydraulic and electric installation of the heat pump (HP), as specified in previous pages, you have to proceed as following.
Page 44
• Screen Gg05 set up CH/HP in manual “MAN” and set up the NOTE! rps (60). Now turn on the heat pump (Mode ON) and wait for some minutes until the compressor icon appears in the lower Some possible malfunctions can be intercepted at the start.
RJ45 (LAN1) port on the back of the K-Touch Panel to a Router or Switch via an Ethernet cable. WARNING! MODBUS cable: Templari HCC cable (similar Belden 3105A 2x22AWG shielded) The MODUS network must always terminate at the ends with a Power cable: 2x1 mmq 120 Ω...
14 HCC connection WARNING! If the plant is designed to directly connected the heat pump to a floor system, such as underfloor heating, without intermediate systems, the absence of condensation is not guaranteed. +24V -24V 13.3 Connecting to the Kita heat pump If you want to use the PGD1 remote control panel at the same time as the K-Touch Panel, you must use a BMS card, purchased separately.
14.1 Exploded view: Plan connection (5a) or BMS connection (5b) +24V -24V PLan CONNESSIONE connection PLan RX-/TX- RX+/TX+ CONNESSIONE BMS connection PLan PLan o BMS? BMS? μPC 220V Morse�o Terra Heat pump terminal quadro macchina board ground connection COM3 COM3 * For data lines with a total lenght of more than 10 meters, insert another 120 Ohm resistance into the last device.
Page 48
Panoramic μPC PLan connection Power supply compact lever connector μPC BMS connection Green/yellow shield ground connection Shield Watch the video for the K-Touch connection to the HCC touch panel connection heat pump.
Page 49
K-Touch panel connected via BMS μPC G + - MODBUS ENDWIDERSTAND TERMINATOR 120Ω RESISTOR 120Ω K-Touch Panel connected via P-LAN as the only display MODBUS Connecting to ground...
15 Control terminal In Kita Split the terminal is assembled on the front of the indoor unit. The terminal of the unit is serially connected by P-LAN line to the outdoor unit. In the control software all the regulation necessary to grant...
15.4 Terminal buttons 4 - Condition of the unit The conditions in which the unit can be are: • OFF • ON • ENERGY S. • AUTO-OFF • AUTO-ON • AUTO-E.S. • Din-OFF • BMS-OFF • ALARM-OFF • PROTECT • BOILER AUTOMATIC MANAGEMENT IF REQUIRED -Alarm Visualize the list of the active alarms.
15.6 Main menu unit we suggest to use the climatic curve instead of setting the Setpoint, because it permits a continuous flow. To enter the menu press the button Mask B03: it permits to activate the program of anti-legionella Press the buttons to navigate manus.
15.9 Clock/timetable menu time set in F3. • F4: it means the timetable from the time set in F3 until the time set in F4. After entering the time in the first time period, confirm with Clock to set the wanted operation mode in the time period concerned (choose between ON - OFF- ENERGY SAVE).
15.10 Input/Output menu Mask D20: Parameters Inverter/Engine Mask D21: Parameters Inverter/Engine Input/Output Masks D30, D31: masks relevant to the external battery fan. You Analog inputs can find the rpm and instantaneous power absorbed. B11 = Condensation: Mask D32: it displays the performances.
Page 56
Gc18: inverter status. generated by PID of the reached water that Gc22: inverter status. activate the integration. • ON-Propor.: it represents the distance from Gc23: inverter status. Gc24: digital inputs the set, in percentage, over that activate Gc25: digital inputs auxiliary integration.
Page 57
• Diff.off HWD: temperature threshold under of the pump (circulator) for the function that integration system for HWD turns off. antifreeze winter. • Delay ON: activation delay of the integration once respected the conditions above. Mask Gfc17: Setpoint on the system temperature...
Page 58
If the previous parameter is active, also the following in fix or intermittent mode in base on the external parameters become editable: temperature. • Res.drain cond.: it enables the activation of • Unit ON: flow water temperature value (sensor B7) that activates the function the resistance for the condensate drain.
Page 59
PWM. of the compressor for DHW production. • Enabling: yes/no • speed: if manual management is active, it shows the • Mode of use: compressor speed for the DHW. • mode Delta T (B7-B4): it tries to keep in automatic the delta set by the circulator Mask Gg06: it enables the defrosting cycle.
16 Alarms Alarm Displayed message Reset Delay Relè Action code ALA01 Sensor B1 broken or disconnected Automatic 60 sec Stop the machine ALA02 Sensor B2 broken or disconnected Automatic 60 sec If present geothermal modulating pump it is set at the top speed...
Page 61
Alarm Displayed message Reset Delay Relè Action Code ALP01 Position: ID1 Flowmeter water After 5 times per At starting: 15s (par. Stop the machine when the maximum time geothermal circ. hours it becomes Hc15) at regime: 5s is reached manual (par.
The letter preceding the numeric digit has the following meaning “AIN” Physic sensors failure uPC “Boh”Alarms that block the circuit, High-Low pressure.. “Compressor” Thermal, envelope “Driver” Electronic valve “Expansion” Alarms uPCe “Fan” “Generic” generic alarms, broken clock, HW, Memory “Humidifier”...
16.2 Notifications Notification causes Heat Transfer Limited It occurs when the difference between the value of the B7 and B2 probes in the case of hrating operation, or the difference between B7 and B3 probes in the case of DHW production, is excessive.
17 Declaration of Conformity Dichiarazione di conformità CE EC Declaration of Conformity EC Konformitätserklärung La so�oscri�a Templari Srl The undersigned Via Pitagora, 20/A – 35030 Rubano (PD) - Italy Die Firma P. IVA 04128520287 conferma che l’apparecchio qui di seguito hereby cer�fies that the following erklärt in alleiniger Verantwortung, dass...