Lindab Plexus Service & Maintenance page 8

Advertisement

Plexus
8
2.2.1 Measure the static nozzle pressure.
To measure the air pressure, a manometer, analog or digital (such as the Lindab
PC410) will be needed.
Insert the measuring tube onto the specialized measuring nozzle
Read off the static nozzle pressure from the manometer
2.2.2 Calculating the airflow
After measuring the static nozzle pressure, read the setting of the four pins in the
corners to find the mean value of the pins.
Locate the diagram on the faceplate or see diagram 1, and use the static nozzle
pressure and the mean value of the pins to find the current airflow.
Plexus S60
Δp
[Pa]
t
120
100
80
70
60
50
40
30
4
5
6
20
Plexus S120
Δp
[Pa]
t
120
100
80
70
60
50
40
30
8
9
10
11
30
40
Plexus L60
Δp
[Pa]
t
120
100
80
70
60
50
40
30
4
5
6
20
We reserve the right to make changes
0
1
2
7
8
9
10
15
30
40
50
0
1
2
13
15
20
25
30
50
60
70
80
100
0
1
2
7
8
9
10
15
30
40
50
Position of JetCone adjustment pins
3
4
5
6
7
8
9
20
25
30
35
40
60
70
80
100
150
Position of JetCone adjustment pins
3
4
5
6
7
8
9
35
40
50
60
70
150
200
250
Position of JetCone adjustment pins
3
4
5
6
7
8
9
20
25
30
35
40
60
70
80
100
150
q
[l/s]
a
3
q
[m
/h]
a
q
[l/s]
a
3
q
[m
/h]
a
q
[l/s]
a
q
[m
3
/h]
a