Installation Instruction; Installation Place Selection - Haier InoSens MRV SI AU032FSEUA Service Manual

Hide thumbs Also See for InoSens MRV SI AU032FSEUA:
Table of Contents

Advertisement

12.2 Installation instruction

In installation, please check specially the below items:
• If the connected units quantity and the total capacity is in the allowable range?
• If the refrigerant pipe length is in the limited range?
• If the pipe size is proper? And if the pipe is installed horizontally?
• If the branch pipe is installed horizontally or vertically?
• If the additional refrigerant is counted correctly and weighed by the standard balance?
• If there is refrigerant leakage?
• If all the indoor power supplies can be on/off simultaneously?
• If the power voltage is in compliance with the data marked on the rating label?
• If the address of indoors has been set?
(1) Before installation
1) Before installation, check if the model, power supply, pipe, wires and parts purchased respectively are correct.
2) Check if the indoors and outdoors can be combined as the following.
Outdoor
Capacity
Combination
Indoor qty
(100w)
type
80
Single
140
Single
180
Single
Notice:
■ Total capacities of indoor units being used ≤ 100% of rated
capacities of outdoor unit.
■ The maximum number and total capacity of indoor units are shown in the table above.If the total capacity of the
indoor units is greater than the rated capacity of the outdoor unit, the actual cooling or heating effect of each
indoor units may not reach its rated capacity.

(2) Installation place selection

Air-conditioner can't be installed in
the place with inflammable gas. Or it
will cause fire hazard.
Indoor
Total indoor capacity
(100w)
4
40-104
8
70-182
9
90-234
The unit should be installed at the
place with good ventilation. No
obstacle at the air inlet/outlet. And
no strong wind blows the unit.
The installation space refers to the
latter info.
indoor capacity
(100W)
total indoor
22
28
36
40
less than 335
45
56
71
The unit should be installed at
the strong enough place. Or it will
cause vibration and noise.
30
branch pipe
capacity
(optional)
(100W)
FQG-B335A