Electrical − High-Static Bh/Bg/Br/B8 Chassis - LG MULTI V ARNU073BGA4 Installation Manual

Ducted indoor units
Hide thumbs Also See for MULTI V ARNU073BGA4:
Table of Contents

Advertisement

GENERAL DATA
Electrical − High-Static BH/BG/BR/B8 Chassis
Model
Voltage Range
BH Units
ARNU073BHA4
ARNU093BHA4
ARNU123BHA4
187-253
ARNU153BHA4
ARNU183BHA4
ARNU243BHA4
BG Units
ARNU073BGA4
ARNU093BGA4
ARNU123BGA4
ARNU153BGA4
ARNU183BGA4
187-253
ARNU243BGA4
ARNU283BGA4
ARNU363BGA4
ARNU423BGA4
BR Units
ARNU283BRA4
ARNU363BRA4
ARNU423BRA4
187-253
ARNU483BRA4
ARNU543BRA4
B8 Units
ARNU363B8A4
ARNU423B8A4
ARNU483B8A4
187-253
ARNU763B8A4
ARNU963B8A4
MCA : Minimum Circuit Ampacity.
MOP : Maximum Overcurrent Protection.
22
Table 10: High-Static BH/BG/BR/B8 Chassis Indoor Unit Electrical Data.
MCA
MOP
Rated Amps (A)
1.32
1.06
1.32
1.06
1.32
1.06
15
1.32
1.06
1.32
1.06
1.32
1.06
3.3
2.65
3.3
2.65
3.3
2.65
3.3
2.65
3.3
15
2.65
3.3
2.65
3.3
2.65
3.3
2.65
3.3
2.65
4.4
3.5
4.4
3.5
4.4
15
3.5
4.4
3.5
4.4
3.5
6.5
5.2
6.5
5.2
6.5
15
5.2
6.5
5.2
6.5
5.2
Units are suitable for use on an electrical system where voltage supplied to unit terminals is within the listed range limits.
Select wire size based on the larger MCA value.
Instead of fuse, use circuit breaker.
Due to our policy of continuous product innovation, some specifications may change without notification.
©LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. "LG" is a registered trademark of LG Corp.
Power Supply
Hz
Volts
Phase
60
208-230
1
60
208-230
1
60
208-230
1
60
208-230
1
Power Input (W)
Cooling
Heating
150
150
150
150
150
150
150
150
150
150
150
150
450
450
450
450
450
450
450
450
450
450
450
450
450
450
450
450
450
450
450
450
450
450
450
450
450
450
450
450
800
800
800
800
800
800
800
800
800
800

Hide quick links: