INSTALLATION MANUAL
AIR
CONDITIONER
Please read this installation manual completely before installing the product.
Installation work must be performed in accordance with the national wiring
standards by authorized personnel only.
Please retain this installation manual for future reference after reading it
thoroughly.
Built - in Duct - Low Static
MFL42803119
Rev.00_051017
Copyright © 2008 - 2018 LG Electronics Inc. All Rights Reserved.
http://www.lghvac.com
www.lg.com

Advertisement

Table of Contents
loading

Summary of Contents for LG MULTI V ARNU073B3G2

  • Page 1 Installation work must be performed in accordance with the national wiring standards by authorized personnel only. Please retain this installation manual for future reference after reading it thoroughly. Built - in Duct - Low Static http://www.lghvac.com www.lg.com MFL42803119 Rev.00_051017 Copyright © 2008 - 2018 LG Electronics Inc. All Rights Reserved.
  • Page 2 IMPORTANT! Please read this instruction sheet completely before installing the product. This air conditioning system meets strict safety and operating standards. As the installer or service person, it is an important part of your job to install or service the system so it operates safely and efficiently. •...
  • Page 3: Table Of Contents

    Ceiling Concealed Duct - Low Static Type Indoor Unit Installation Manual TABLE OF CONTENTS Installation Requirements Required Parts Required Tools Safety Precautions....4 Introduction......7 o Level gauge Installation o Four type "A" screws o Screw driver o Connecting cable o Electric drill o Hole core drill Selection of the best location ..........8...
  • Page 4: Safety Precautions

    Safety Precautions Safety Precautions To prevent injury to the user or other people and property damage, the following instructions must be followed. n Be sure to read before installing the air conditioner. n Be sure to observe the cautions specified here as they include important items related to safety. n Incorrect operation due to ignoring instruction will cause harm or damage.
  • Page 5 Safety Precautions • Do not modify or extend the power cable. - There is risk of fire or electric shock. • Do not let the air conditioner run for a long time when the humidity is very high and a door or a window is left open.
  • Page 6 Safety Precautions Installation • Always check for gas (refrigerant) leakage after installation or repair of product. - Low refrigerant levels may cause failure of product. • Install the drain hose to ensure that water is drained away properly. - A bad connection may cause water leakage. •...
  • Page 7: Introduction

    Introduction Introduction Symbols Used in this Manual This symbol alerts you to the risk of electric shock. This symbol alerts you to hazards that could cause harm to the air conditioner. NOTICE This symbol indicates special notes. Features Built-in Duct type Suction Grille Wired Remote Controller TE MP...
  • Page 8: Installation

    Installation Installation Selection of the best location Indoor unit Top view Install the air conditioner in the location that satisfies the fol- [Unit: mm(inch)] Airflow lowing conditions. • The place shall easily bear a load exceeding four times the Inspection hole indoor unit’s weight.
  • Page 9: Ceiling Opening Dimension And Hanging Bolt Location

    Installation B4: 1,118mm(44 inch) B3: 840mm(33-1/16 inch) B3/B4: 295mm(11-3/5 inch) (Ceiling opening) (Ceiling opening) Ceiling dimension and hanging bolt location Installation of Unit Install the unit above the ceiling correctly. CASE 1 POSITION OF SUSPENSION BOLT • Apply a joint-canvas between the unit and duct to absorb unnecessary vibration.
  • Page 10: Indoor Unit Installation

    Installation Indoor Unit Installation • Select and mark the position for fixing bolts. • Insert the set anchor and washer onto the suspen- • Drill the hole for set anchor on the face of ceiling. sion bolts for locking the suspension bolts on the ceiling.
  • Page 11 Installation CAUTION : The connecting cable connected to the indoor and outdoor unit should be complied with the fol- lowing specifications (This equipment shall be provided with a cord set complying with the national regulation). 10±3mm AWG18 If the supply cord is damaged, it must be replaced by a special cord or assembly available from the manufacturer of its service agent.
  • Page 12: Part Name And Functions

    Installation Part name and functions Air outlet Air outlet Suction Grille Suction Grille Suction Canvas • Buit-in duct type with Suction Grille. • Buit-in duct type with Suction Grille and Suction Canvas. n B3/B4 Series : Built-in Duct type Control Box service Indoor Unit...
  • Page 13: Plumbing Materials And Storage Methods

    Installation Plumbing materials and storage methods Pipe must be able to obtain the specified thickness and should be used with low impurities. Also when handling storage, pipe must be careful to prevent a fracture, deformity and wound. Should not be mixed with contaminations such as dust, moisture. Refrigerant piping on three principles Drying Cleanliness...
  • Page 14 Installation Nitrogen substitution method Welding, as when heating without nitrogen substitution a large amount of the oxide film is formed on the internal piping. The oxide film is a caused by clogging EEV, Capillary, oil hole of accumulator and suction hole of oil pump in compressor. It prevents normal operation of the compressor.
  • Page 15: Checking The Drainage

    Installation INSULATION, OTHERS Insulate the joint and tubes completely. THERMAL INSULATION All thermal insulation must comply with local requirement. INDOOR UNIT Union for gas pipe Refrigerant pipe and thermal Thermal insulator for refrigerant pipe insulator(Local supply) (Local supply) Thermal insulator for piping(Local supply) Hose clip for thermal insulator (Local supply)
  • Page 16: Drain Piping

    Installation CAUTION 1. Install declination of the indoor unit is very important for the drain of the duct type air conditioner. 2. Minimum thickness of the insulation for the connecting pipe shall be 19mm. Front of view • The unit must be horizontal or declined to the drain hose connected when finished installation.
  • Page 17 Installation CAUTION : The supplied flexible drain Flexible drain hose Flexible drain hose Flexible drain hose hose should not be curved, neither 1/50~1/100 screwed. The curved or screwed hose MAX 700mm may cause a leakage of water. (27-9/16 inch) CAUTION: After the confirmation of the above conditions, prepare the wiring as follows: 1) Never fail to have an individual power specialized for the air conditioner.
  • Page 18 Installation WIERED REMOTE CONTROLLER INSTALLATION • Since the room temperature sensor is in the remote controller, the remote controller box should be installed in a place away from direct sunlight, high humidity and direct supply of cold air to maintain proper space temperature. Install the remote controller about 5ft(1.5m) above the floor in an area with good air circulation at an average tempera- ture.
  • Page 19: Dip Switch Setting Of Indoor Unit Pcb

    Installation Dip Switch Setting of Indoor unit PCB Function Description Setting Off Setting On Default Communication N/A (Default) Cycle N/A (Default) Group Control Selection of Master or Slave Master Slave Dry Contact Mode Selection of Dry Contact Wired/Wireless remote Mode controller Auto Selection of Manual or Auto...
  • Page 20: Group Control Setting

    Installation Group Control Setting 1. Group Control 1 n Wired remote controller 1 + Indoor units LGAP Network System Slave Master Slave Slave Signal 12 V Display Error Message Only connect serial signal and GND lines between slave indoor unit Master n Dip Switch in PCB (Cassette and Duct Type indoor units) Master Setting...
  • Page 21 Installation 5. In case of any error occurs at indoor unit, display on the wired remote controller. Exception of the error indoor unit, an individual indoor unit control possibility. 6. In case of Group Control, it is possible to use following functions. - Selection of operation options (operation/stop/mode/set temperature) - Control of flow rate (High/Middle/Low) - It is not possible at some functions.
  • Page 22 Installation 3. Group Control 3 n Mixture connection with indoor units and Fresh Air Intake Unit LGAP Network System Signal Master Slave Master Slave 12 V Display Error Message Master Master h In case of connecting with standard indoor unit and Fresh Intake Unit, separate Fresh Air Intake Unit with standard units.
  • Page 23 Installation 4. 2 Remote Control n Wired remote controller 2 + Indoor unit 1 LGAP Network System Master Display Error Message Master Slave 1. It is possible to connect two wired remote controllers with one indoor unit. 2. Every types of indoor unit is possible to connect two remote controller. 3.
  • Page 24 Installation 5. Accessories for group control setting It is possible to set group control by using below accessories. Indoor unit 2 EA +Wired remote controller Indoor unit 1 EA +Wired remote controller 2EA h PZCWRCG3 cable used for connection h PZCWRC2 cable used for connection S lave Mas te r PZC WRC 2...
  • Page 25 Installation ARNU073B3G2+PBSGB30(Accessory), PBSC30(Accessory) ARNU093B3G2+PBSGB30(Accessory), PBSC30(Accessory) ARNU123B3G2+PBSGB30(Accessory), PBSC30(Accessory) ARNU153B3G2+PBSGB30(Accessory), PBSC30(Accessory) (Unit;cmm(cfm)) Static Pressure(mmAq (in.Aq)) Setting Value 0(0) 1(3.93) 2(7.87) 3(0.11) 4(0.15) 6.29(222) 3.03(107) 0.93(32) 6.61(233) 4.84(170) 1.52(53) 7.69(271) 5.64(199) 2.18(76) 0.79(27) 8.19(289) 6.28(221) 2.81(99) 0.85(30) 8.91(314) 7.43(262) 4.96(175) 1.58(55) 9.51(335) 8.14(287) 5.91(208) 2.75(97) 0.95(33)
  • Page 26 Installation ARNU073B3G2+PBSGB30(Accessory), PBSC30(Accessory) ARNU093B3G2+PBSGB30(Accessory), PBSC30(Accessory) ARNU123B3G2+PBSGB30(Accessory), PBSC30(Accessory) ARNU153B3G2+PBSGB30(Accessory), PBSC30(Accessory) Lower Limit of External Upper Limit of External Standard Capacity Mode Set value ESP(mmAq (in.Aq)) cmm(cfm) Static Pressure(mmAq (in.Aq)) Static Pressure(mmAq (in.Aq)) 8(283) High 4(0.15) 6.5(229) 2(7.87) (factory set) 5.5(194) 8(283) 4(0.15) 6.5(229) Standard...
  • Page 27 Please call the installing contractor of your product, as warranty service will be provided by them. Service call Number # : (888) LG Canada, (888) 542-2623 CANADA Numéro pour les appels de service : LG Canada, 1-888-542-2623...