System Application #5- Cascade System with DHW Indirect Tank (for Low DHW Demand)
Supply
Air separator
Cold water
Backflow
preventer
Expansion tank
Return
In this configuration, space heating and DHW can operate simultaneously.
Note
The aquastat on the DHW indirect tank must be connected to a sub unit.
If a dedicated sub unit is used, the input capacity requirement of the indirect tank shall not exceed
the capacity of the single boiler.
Connect the DHW pump to the sub unit.
Connect zone pumps to the zone controller. Do not connect zone pumps to the main or sub units.
System Application 6 - Cascade System with DHW Indirect Tank (for Low DHW Demand)
Supply
Return
Temperature
sensors (required)
Dirt collector
Hydro/Air separator
In this configuration, space heating and DHW can operate simultaneously.
Note
The aquastat on the DHW indirect tank must be connected to a sub unit.
If a dedicated sub unit is used, the input capacity requirement of the indirect tank shall not exceed
the capacity of the single boiler.
Connect the DHW pump to the sub unit.
Connect zone pumps to the zone controller. Do not connect zone pumps to the main or sub units.
Main
Temperature
sensors (required)
Main
Backflow preventer
Expansion tank
Sub1
Sub2
Sub2
Sub1
Cold water
Installing a Cascade System
DHW
Indirect
tank
Aquastat
Cold water
DHW
Indirect
tank
Aquastat
Cold water