Planning; System Structure - Pepperl+Fuchs K-LB Series Manual

Surge protection barriers
Table of Contents

Advertisement

Functional Safety K-LB-*.*, F*-LB-I, P-LB-*.*.*

Planning

3
Planning
3.1

System Structure

3.1.1
Low Demand Mode of Operation
If there are two control loops, one for the standard operation and another one for the functional
safety, then usually the demand rate for the safety loop is assumed to be less than once
per year.
The relevant safety parameters to be verified are:
the PFD
and the T
the SFF value (Safe Failure Fraction)
the HFT architecture (Hardware Fault Tolerance)
3.1.2
High Demand or Continuous Mode of Operation
If there is only one safety loop, which combines the standard operation and safety-related
operation, then usually the demand rate for this safety loop is assumed to be higher than
once per year.
The relevant safety parameters to be verified are:
the PFH value (Probability of dangerous Failure per Hour)
Fault reaction time of the safety system
the SFF value (Safe Failure Fraction)
the HFT architecture (Hardware Fault Tolerance)
10
value (average Probability of dangerous Failure on Demand)
avg
value (proof test interval that has a direct impact on the PFD
1
value)
avg

Advertisement