Sol-Ark 5K Error Codes

Fault
Instruction
F1
DC Inversed Failure
F8
GFDI_Relay_Failure
Grid_Mode_change
F13
AC_OverCurr_Failure
F15
GFCI_Failure
F16
Tz_Ac_OverCurr_Fault
F18
F20
Tz_Dc_OverCurr_Fault
F22
Tz_EmergStop_Fault
Tz_GFCI_OC_Fault
F23
F24
DC_Insulation_Fault
AC_Active_Batt_Fault
F25
BusUnbalance_Fault
F26
F29
Parallel_CANBus_Fault
F30
AC_MainContactor_Fault
F31
Soft_Start_Failed
AC Overload Fault
F34
F35
AC_NoUtility_Fault
F37
DCLLC_Soft_Over_Cur
F39
DCLLC_Over_Current
F40
Batt_Over_Current
F41
Parallel_System_Stop
F45
AC_UV_OverVolt_Fault
Parallel_Aux_Fault
F46
F47
AC_OverFreq_Fault
F48
AC_UnderFreq_Fault
F55
DC_VoltHigh_Fault
DC_VoltLow_Fault
F56
F58
BMS communication fault
F60
Gen_Volt_or_Fre_Fault
F61
Button_Manual_OFF
F63
ARC_Fault
F64
Heatsink_HighTemp_Fault
If you have parallel systems and turn one system off, you with get this notification. Not a fault.
Current Leakage from inverter AC output to Ground, check Ground and neutral are connected at the main
panel
It can happen when not using batteries or if Grid Input settings are changed. This is a notification, NOT a
fault. If you switch from No Batt to Battery mode, Power the System down completely to restart.
It is usually caused by Loads too large for the inverter. If off-grid, the battery discharge amps are
programmed too low. Overloads can result in F15, F18, F20, or F26.
Ground fault. Check PV+ or PV- wiring (which must be ungrounded). Exposed PV conductors + rain can also
cause. Check that the neutral line and Ground are not double-bonded (common with portable generators).
Overloaded the Load Output: reduce loads. Wiring Short on the AC Side can also cause this error. Overloads
can result in F15, F18, F20, or F26.
It is typically caused by DC current from the battery that is too large (ex: 4 Ton AC Unit). Overloads can
result in F15, F18, F20, or F26.
Initiated Emergency Stop; see sensor pinout table.
PV Ground fault. Check PV+ or PV- wiring (which must be ungrounded or damage can occur). Typically
caused by pinched PV wire grounding the PV+ or PV-. Grounded PV wire can cause F20, F23, or F26.
An exposed PV conductor combined with moisture is faulting (can cause F16, F24, F26).
No battery connection to the Inverter and Activate Battery is enabled. Disable Activate Battery in settings
while no battery is connected.
Too much load on one leg (L1 or L2) Vs. the other leg or DC loads on the AC output when off-grid. Grounded
PV wire can cause F20, F23, or F26.
Usually, a communication error for parallel systems, check cables and MODBUS addresses
Contact Sol-Ark.com
Soft Start of large motor failed
AC Overload or load shorted. Reduce heavy loads.
Grid connection lost
Software DC overcurrent
Hardware DC overcurrent
Batteries exceeded their current discharge limit
If one system faults in parallel, this normal fault will register on the other units as they disconnect from grid
Grid under voltage causes a disconnect. This will self-reset when grid stabilizes.
Cannot communicate with other parallel systems. Check Master = 1, Slaves are 2-9, ethernet cables are
connected.
Grid over Frequency (common in power outages) causes a disconnect. Will self-reset when grid stabilizes.
Grid under Frequency (common in power outages) causes a disconnect. Will self-reset when grid stabilizes.
PV may be higher than 500V. Battery voltage should not be above 59V or 63V (depending on the model).
Batteries are overly-discharged, or Lithium BMS has shut down. If battery settings are off, this can also
happen.
Sol-Ark is programmed to BMS Lithium Battery Mode but cannot communicate with a BMS
Generator Voltage or Frequency went outside the allowable range
The parallel Slave system turned off without turning off Master
It can be a lousy PV connector/connection. And sometimes a false alarm due to powerful lightning storms.
Check the built-in fans are running; ambient temp may be too high
January 26
Common Cause/Remedy
th
, 2022
42

Hide quick links:

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the 5K-P and is the answer not in the manual?

Subscribe to Our Youtube Channel

This manual is also suitable for:

Tc10324rDg224nrk

Table of Contents