Wiring Diagrams; Amerex Wiring Plan View - Accurex XBEW Installation, Operation And Maintenance Manual

Table of Contents

Advertisement

Wiring Diagrams

Amerex Wiring Plan View

INSTALLER PROVIDED
JUNCTION BOXES
BASIC WIRING DIAGRAM
RED (COMMON)
YELLOW (N.O)
BASIC WIRING DIAGRAM
RED (COMMON)
YELLOW (N.O)
NOTES:
1.
DENOTES FIELD INSTALLATION
2.
DENOTES FACTORY INSTALLATION
3. GAS VALVE: UL LISTED ELECTRICALLY-OPERATED SAFETY VALVE FOR NATURAL OR LP GAS AS NEEDED OF
APPROPRIATE PRESSURE AND TEMPERATURE RATING, 110V/60HZ OR AMEREX GAS VALVES, PN 12870, 12871,
12872, 12873, 12874, 12875 AND 12876.
4. K1a AND K1b ARE N.0. WHEN K1 IS DE-ENERGIZED.
POWER SOURCE
PRM
MICROSWITCH
POWER SOURCE
BLACK (N.C.)
NOTE: DO NOT USE YELLOW WIRE ON MICROSWITCH IN NORMAL
MICROSWITCH
INSTALLATION. THE YELLOW WIRE IS TO BE USED ONLY FOR
EXTINGUISHER ALARM, LIGHTS, CIRCUITS, ETC.
L1
115V/60HZ
L2
BLACK (N.C.)
MICROSWITCH
MANUAL RESET RELAY
ELECTRIC GAS VALVE
MANUAL RESET
RELAY
MANUAL RESET RELAY
K1
Ka
K1b
CURRENT DRAW MAX:
8A RESISTIVE
8A INDUCTIVE
115VAC
Kitchen Hoods • Type I and Type II
GAS VALVE
PUSHBUTTON SWITCH
GAS VALVE
SEE NOTE 3
23

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

XxewXgewXbdwXxdwXgdwXbev ... Show all

Table of Contents