USING THE QUICK GUIDE
Provides information on handling, assembly and installation.
Remains for later use at the product.
Does not replace the electronically provided instructions for use.
This manual is intended exclusively for persons who are familiar with the logistics and installation. The person must have the
following qualifications:
Knowledge and understanding of the safety instructions.
Skills for installation and assembly.
Knowledge of EMC-conform wiring.
Detection of hazards and risks of the electrical drive technology.
Knowledge of IEC 60364-5-54.
Knowledge of national safety regulations.
SAFETY INSTRUCTIONS
DANGER
Interventions by unauthorized personnel !
Danger to life through electric shock and malfunctions !
► Modification or repair is only permitted by KEB authorized personnel.
Getting more documentation
NOTICE
Hazards and risks through ignorance.
► Open the KEB homepage at www.keb.de.
► By entering the material number in the search field, you will get the corresponding parts of the
instructions for use.
Read the instructions for use carefully !
► Observe the safety and warning instructions !
► If you have any questions, please contact
service@keb.de
TRANSPORT
The transport must be carried out by instructed persons, observing the following instructions.
CAUTION
Maximum design edges and high weight !
Contusions and bruises!
► Never stand under suspended loads.
► Wear safety shoes.
► Secure devices accordingly when using lifting gear.
NOTICE
Behaviour in case of transport damage
► When receiving goods, check the device for transport damage such as deformations or loose parts.
► In case of damage, contact the carrier immediately.
► Do not operate the device in case of transport damage!
STORAGE
Do not store the devices
in the environment of aggressive and/or conductive liquids or gases.
at places with direct sunlight.
outside the specified environmental conditions.
UNPACKING AND CHECKING
Make sure that no components are bent and/or isolation distances are changed.
The device must not be put into operation in case of mechanical defects. There is no compliance with applicable safety
standards any more.
INSTALLATION
If available, use the lifting eyebolts provided for installation.
Do not stand under suspended equipment during installation.
Mount the product according to the required degree of protection.
Make sure that no small parts fall into the device during assembly and wiring (drilling chips, screws etc.). This also applies to
mechanical components, which can lose small parts during operation.
The devices are intended for the use in a pollution degree 2 environment.
Maximum ambient temperature 45°C
UL / CSA: Ensure UL-compliant connection of all power connections according to the requirements given in the data
sheet.
MOUNTING DIMENSION FOR THE USE AS SIDE MOUNT FILTER
Minimum distances
D
F
B
The mounting dimension of the drive controller apply when used as back mount filter.
WIRING
L3
L2
L1
PE
1:
Mains fuse
!
2:
Mains contactor
CONNECTION
Part No.
L1, L2, L3
14E6T60-1050
16E6T60-1050
18E6T60-1050
Spring-
loaded
20E6T60-1050
terminal
22E6T60-1050
FUSE PROTECTION
Part No.
14E6T60-1050
16E6T60-1050
18E6T60-1050
20E6T60-1050
22E6T60-1050
Part No.
14E6T60-1050
16E6T60-1050
18E6T60-1050
20E6T60-1050
22E6T60-1050
Dimension
Dimension in mm
A
0
B
100
A
E
C
30
D
0
D
C
E
0
F
1)
1)
Distance to front operating elements in the control cabinet
door.
Mains connection 3-phase (L1, L2, L3)
➀ ➁
L3
L3'
L3
L3
L2
L2'
L2
L2
L1
L1'
L1
L1
3:
Mains choke
5: Drive controller
4:
E6 filter
Cross-sec-
Cross-sectional area
Connection
tion
Tightening torque
in mm² / AWG
PE
Output
L1, L2, L3
PE
Output
L1, L2, L3 PE
0.2...6 / 24...10
6 / 10
Spring-
0.75...25 / 18...4
10 / 8
loaded
4...35 / 14...2
16 / 6
terminal
Strand
4...35 / 14...2
35 / 2
Betatherm
M6 bolt for
10...50 /
50 /
crimp
8...1/0
1/0
connector
Fuse protection for IEC
Max. fuse size
Input voltage
Class gG
SCCR 30 kA
25 A
50 A
400 V
80 A
100 A
160 A
Fuse protection for UL
Max. fuse size
Class RK5
Class gG
Input voltage
SCCR
SCCR 30 kA
5 kA
10 kA
25 A
25 A
50 A
50 A
63 A
60 A
60 A
480 V
100 A
90 A
90 A
125 A
125 A
The fuse values of the filters correspond to the fuse values of the corresponding drive controllers.
Distance in inches
0
Cable cross-sections and fuses must be dimensioned according to the design of the machine manufacturer. Specified
minimum / maximum values may not be fallen below /exceeded.
4
1.2
USE ON THE DRIVE CONTROLLER
0
The mechanical housing sizes of the COMBILNE E6 back mount filters correspond to those of the COMBIVERT F6 drive
0
controllers.
COMBILINE E6
2 (14E6T60-1050, 16E6T60-1050)
Housing
3 (18E6T60-1050, 20E6T60-1050)
4 (22E6T60-1050)
START-UP AND OPERATION
WARNING
Triggering of overcurrent protection devices
Risk of fire or electric shock!
► Triggering of an overcurrent protection device will be a hint for an overload or short circuit. Triggering
a RCD may be caused by a leakage current.
► In order to reduce the risk of fire or electric shock, live parts and other components of the device
should be checked and replaced in case of damage.
CAUTION High temperatures on the device
Burning of the skin !
► Cover hot surfaces so that they are safe to touch.
► If necessary, attach warning signs to the system.
► Check surface before touching.
► Let the device cool down before any work is carried out.
MAINTENANCE
The following maintenance work has to be carried out when required, but at least once a year by authorized and trained
personnel.
► Clean the product from dirt and dust deposits.
Output
► In case of malfunction, unusual noises or smells inform a person in charge!
► In case of failure, please contact the machine manufacturer.
INSTALLATION / ELECTRICAL CONNECTION
DANGER
Voltage at the terminals and the device !
10 /
88
Danger to life by electric shock !
Never work under voltage on the device or touch exposed parts.
► For any work on the unit switch off the supply voltage and secure it against switching on.
► Wait until the drive has stopped in order that no regenerative energy can be generated.
► Never bridge upstream protective devices (also not for test purposes).
Connect the protective earth conductor properly.
► Install all required covers and protective devices for operation.
For a trouble-free and safe operation, please pay attention to the following note:
► Check for reliable fit of the device connections in order to avoid contact resistance and sparking.
DISPOSAL
► For professional disposal, follow the instructions in the instructions for use
Type
SIBA 50 140 06.25
SIBA 50 140 06.50
SIBA 20 189 20.63
COOPER BUSMANN
170M1365
LITTELFUSE
L70QS060
SIBA 20 189 20.100
COOPER BUSMANN
170M1367
LITTELFUSE
L70QS090
SIBA 20 189 20.125
COOPER BUSMANN
170M1368
COMBIVERT F6
2
3
4

Advertisement

loading

Summary of Contents for KEB COMBILINE E6 Series

  • Page 1 Risk of fire or electric shock! Mains connection 3-phase (L1, L2, L3) ► Modification or repair is only permitted by KEB authorized personnel. ► Triggering of an overcurrent protection device will be a hint for an overload or short circuit. Triggering ➀...
  • Page 2 ISO 7092 - 6 - 200 HV 70 lb inch 22E6T60-1050 Instructions for use Installation COMBILINE E6 EMC filter www.keb.de/fileadmin/media/Manuals/dr/ma_dr_e6-filter_inst_20165077_de.pdf KEB Online www.keb.de 다른 언어도 사용할 수 있습니다. Други налични езици. Ostali dostupni jezici. 其他语言可用。 Más elérhető nyelvek. Jiné jazyky k dispozici.

This manual is also suitable for:

14e6t60-105016e6t60-105018e6t60-105020e6t60-105022e6t60-1050