Econar GeoSource Invision 3 Q Series Installation And Operating Instructions Manual page 5

Dual circuit, vertical forced air
Table of Contents

Advertisement

earth
loop water temperatures.
Typical
electric hot water
heaters
supply
16,720
Btu/hr
(4.9
kwhr)
of
capacity.
The
heat
pump
heats the
DHW
by
circulating
the water
from
the
storage
tank through
a
double-walled,
refrigerant-to-water
condenser
coil.
When
the
temperature
of
the water
in
the
storage
tank drops below
a
reset
point
of
113"F,
a
pump,
built
into
the heat
pump,
circulates
the
water
and the
number
two
compressor
starts.
The compressor continues to run, heating
the
DHW,
until
the
water
reaches
1l9oF.
The
DHW
pump
is
controlled
to
run continuously
only
when
the
compressor
is activated
in
DHW
mode.
This pump
will
also
run
for
a
one
minute sampling period every
seven
minutes to
continuously
sample the
tank's
water temperature
and
bring
the
compressor on
at the
correct
times.
The tank
temperature
is
controlled with
a
simple temperature
sensor
mounted on
a
copper pipe inside
the heat
pump.
The
minimum
entering water temperature on
the
DHW
side (water
in
the storage
tank) is 50oF. Startup on
the
system
with
colder water
will
require restricting
flow
to
the
unit until
tank
temperatures
rise. A
maximum
DHW
tank temperature
of
126oF
is also specified to
keep the
system
from locking
out
on
high
head pressure.
Figure 4
shows the
required
plumbing
to connect
the system.
Figure 5
shows an
example
of
a
plumbing circuit for
a
-DWR
unit
that
has
enough
capacity
for
both domestic
hot water
and
radiant
floor
heating.
Figure 6
shows
a
plumbing circuit
for
a
-DWR
unit
that is
sized
to
full
capacity
for
radiant
floor
heating. With this
setup, the
-DWR
unit
can
provide
supplemental domestic hot water
to
an
additional water
heater
when
the
radiant
floor
is
not
utilizing
the
full load.
Reduced
flow
rates and increased
leaving water
temperatures can
lock
the
DHW
circuit
out
on
rhe
high
pressure
switch,
so
follow
the
plumbing
dia-eram
closely.
of
30 gallons is required;
normally
a
50
to
80
gallon tank
would
be used.
When
installing
a
GeoSource
Invision3 with
the
-DWR
option,
use
an
indirectly fired
water
heater
as
a storage
tank (shown
in
Figures 5
and
6).
The electric
elements can be
left
in
and
wired
to
provide
backup water heating
ability,
but be
sure
to
leave the
circuit
breaker
off
during normal operation,
so
that
it
does
not interfere
with
tank
temperatures.
€Note:
While all
hot water tanks
are
insulated on
the
top
and sides,
many do not
have
insulation on
the
bottom" An
insulated
pad beneath
uninsulated
tanks
will
reduce
ener-qy
loss
to
the
floor.
Always
check
local
codes
to
be sure
hot water
tanks can
be used
for
this
purpose.
2.
DHW Pump
The
DHW
pump
transfers the
energy supplied
by
the
GeoSource
Invision'heat
pump to the
storage
tank.
This
pump is impedance protected
and does
not require
additional
fusing. A
two-amp
inline
fuse is supplied on
the
pump
for additional
safety
and
for
use
as
a shut
off
switch.
This pump
has
been sized
to
provide
the
required
flow
to
the heat
exchanger
with
a
total
system pressure
drop
of
2
1
feet
ofhead.
This
pressure
drop
can be
calculated
from
the
total
pressure
drop through *re
piping,
added
to
the
pressure
drop
of
the heat
pump
of
15
feet
of head.
Figure
3
shows the
pump curve
of
the
DHW
pump.
The pump
can
provide
8
GPM
at
2l
feetof
head.
Using
one
inch
copper pipe is
critical
to
maintain
the
proper
flow.
The
remaining six feet
of
head
is equivalent
to
100
feet
of
one
inch type
L
copper tubing or
a
combination
of
straight
pipe
and
fittings.
If
extremely long
distances separate the
heat
pump
and storage
tank,
or
ifadditional
pressure
drop
cannot
be
avoided,
a
booster
pump must
be added
to
the
plumbing system. For
the
most
efficient
operation, locate
the heat
pump
and storage
tank
as
close together
as
possible
and
insulate
all
water
piping.
A
common problem
with circulator
pumps is trapped
air
in
the
system.
This air accumulates
in
the
suction port
of
the
circulator
pump,
causing
cavitation in
the
pump.
The
cavitation
can
stop
the
flow of
water
and
leadio
premature pump
failure
and
noisy
operation.
The air
can
be
eliminated by completely
purging
the system
or
by
placing
an
air
separator
in
the
plumbing
lines.
The entire
system
must
be
purged
of
air
during
initial
installation. Normal
systems
will
operate
on
iater
supply
pressure,
which
keeps
air
from
reentering
the
system.
If
a
system
is not
working
on water supply
pressure,
maintain
110
to
30
psi static
pressure
to
keep
air out
of
the
loop.
Otherwise, corrosion, bacteria
growth,
or pump cavitation
may occur.
An
operating temperature
range
for
the
earth
loop
side
of
the heat
pump is also specified
as
follows:
-
20"F
(minimum for
heating)
-
100"F
(maximum for cooling)
-
80"F (maximum
for
-DHW
and
-DWR option)
These
limits
have been established based
on
efficiency
limitations
and safety pressure
switch
limits
(50_psi low_
pressure
curout
and
580 psi high-pressure
cutout). DHW
operation is
limited to
80nF
because at
this warm
of
a
source
temperature,
the
heating capacity
increases
to
the
point of
overloading
the
water-cooled
condenser,
tripping
the system
offon
high
head pressure.
eNote: After all plumbing
and
purging
of the
circuit
is
complete;
MOVE DIp SWITCH
#4,
Iocated
on
the
controller,
to the ON position to
initiate
DHW
operation. Allowing
the
pump to run
dry
will
damage
the
circulating
pump
and
overheat
the
motor.
1.
Storage Tanks
Insulated electric hot water
heaters are used
for
storage
tanks
for
the
DHW circuit of
the heat
pump.
A
minimum
3

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents