CPS1200EILCD/CPS2200EILCD
User's Manual
IMPORTANT SAFETY INFORMATION
(SAVE THESE INSTRUCTIONS)
This manual contains important safety instructions. Please read and follow all instructions carefully
during installation and operation of the unit. Read this manual thoroughly before attempting to unpack,
install, or operate the inverter.
Insure the wall outlet and inverter are located near the equipment being attached for proper accessibility.
To reduce risk of damage and injury, please use batteries with good quality.
Provide adequate ventilation for the battery compartment. The battery enclosure should be designed to
prevent accumulation and concentration of hydrogen gas at the top of the compartment.
DO NOT expose the inverter to rain, snow or liquids of any type. The inverter is designed for indoor use
only.
DO NOT obstruct the ventilation openings.
DO NOT connect neutral of the power distribution box on the wall to:
(a) The OUTPUT neutral of inverter.
or (b) The INPUT neutral of equipment.
Otherwise the reversed polarity will damage the inverter and the connected equipment.
CAUTION! Risk of electric shock, do not remove cover. No user serviceable parts inside.
The battery can energize hazardous live parts inside even when the AC input power is disconnected.
To avoid electrical shock, turn off the inverter and unplug it from the AC power source before servicing
the battery. Servicing the battery can only be performed by trained personnel.
INSTALLING YOUR HOME UPS SYSTEM
UNPACKING
Inspect the unit upon receipt. The box should contain the following:
Unit1; Power Cord1; User Manual1
HOW TO DETERMINE THE POWER REQUIREMENTS OF YOUR EQUIPMENT
1. Insure that the equipment plugged into the AC outlet does not exceed the inverter unit's rated
capacity (1200VA/720W for CPS1200EILCD; 2200VA/1320W for CPS2200EILCD). If rated unit
capacities are exceeded, an overload condition may occur and cause the HOME UPS unit to shut
down or the circuit breaker trip.
2. If the power requirements of your equipment are listed in units other than Volt-Amps (VA), convert
Watts (W) or Amps (A) into VA by doing the calculations below. Note: The below equation only
calculates the maximum amount of VA that the equipment can use, not what is typically used by the
equipment at any one time. Users should expect usage requirements to be approximately 60% of
below value.
TO ESTIMATE POWER REQUIREMENTS
1. 220 V x
Amps (A) =
VA
2. Add the totals up for all pieces of equipment and multiply this total by 0.6 to calculate actual
requirements. There are many factors that can affect the amount of power that your computer system
will require. The total load that you will be placing on the battery-powered outlets should not exceed
80% of the unit's capacity.
HARDWARE INSTALLATION GUIDE
Before installation, please read and understand the following instructions:
1.
Placement
The inverter must be installed in a protected environment away from heat- emitting appliances such
as a radiator or heat register. Do not install this product where excessive moisture is present.
All manuals and user guides at all-guides.com
2.
Ventilation
The location should provide adequate air flow around the inverter with 10 CM minimum clearance
on all sides for proper ventilation.
3.
Connect the Battery
Connect the external battery with the DC cables
from the back of the inverter. Follow battery
polarity guide located near battery cables as
below.
"+" Red cable for battery positive polarity;
"-" Black cable for battery negative polarity.
4.
Connect to AC and Charge the Battery
Connect the inverter to a wall outlet. Avoid using extension cords and adapter plugs. Charging the
battery for at least 8 hours is recommended to insure that the battery is fully charged. To recharge
the battery, simply leave the unit plugged into a wall outlet. To maintain optimal battery charge,
leave the inverter plugged into an AC outlet at all times.
This unit can be charged even when it is not turned on.
5.
Connect the Load
Connect the equipment to the inverter outlet. Please make sure that the total loads of your
equipments are less than the maximum total power load of the inverter.
FRONT PANEL DESCRIPTION
1.
LCD Module Display.
High resolution and intelligent LCD display shows all the inverter information with icons and
messages. For more information please check the "Definitions for Illuminated LCD Indicators"
section.
2.
Power Switch
Press the power switch to turn the inverter ON or OFF.
3.
LCD Function Selected Switch
The switch can be used to select the LCD display contents including input/output voltage and load
percentage, etc.
REAR PANEL DESCRIPTION
1.
DC Input Cable (Black)
Connect to battery negative polarity.
2.
DC Input Cable (Red)
Connect to battery positive polarity.
3.
Input Circuit Breaker
The circuit breaker provides optimal overload protection.
BASIC OPERATION

Advertisement

loading

Summary of Contents for CyberPower CPS1200EILCD

  • Page 1 1. Insure that the equipment plugged into the AC outlet does not exceed the inverter unit’s rated REAR PANEL DESCRIPTION capacity (1200VA/720W for CPS1200EILCD; 2200VA/1320W for CPS2200EILCD). If rated unit capacities are exceeded, an overload condition may occur and cause the HOME UPS unit to shut down or the circuit breaker trip.