Download Print this page

Siemens MKB-1 Operating Instructions Manual page 12

Mxl multi-line keyboard/display panel
Hide thumbs Also See for MKB-1:

Advertisement

Supervisory
Siemens Building Technologies
Fire Safety
Supervisory Annunciation
When a supervisory is detected, the System causes the SUPERVISORY LED on the
MKB to flash, the System's internal audible to sound, and the display on the MKB to
display the event in the following format:
40 Characters
1
SUP CUSTOM MESSAGE
2
SUP CUSTOM MESSAGE
3
4
5
6
7
8
9
SUP CUSTOM MESSAGE
10
ALR=000, SUP=002, TBL=000, SEC=000
11
SIEMENS BUILDING TECHNOLOGIES
12
13
1-001
14
002
15
11:59:59 Dec 31, 02
Example shown is Canadian Display
Figure 6
SUPERVISORY Event Screen With More Info Key Pressed
In addition, the System responds to supervisories with programmed output functions.
In Figure 6, 1-001 represents the address of the device reporting the supervisory.
002 on Line 14 in the More Info area (Lines 13-15) tells you that this is the second
(and the most recent) of two supervisories received. The status information shown in
Line 10 reports the total of alarms, supervisories, troubles, and security conditions.
If your System includes a printer, it prints a message from two to four lines long
similar to the following:
SUPERV
1-1
#2 [custom message], [device type]
IN
IN
IN
12:01:22 Dec 31, 02
(002 / 002)
11:59:59 Dec 31, 20
12
P/N 315-048692-2