MODEL 5318B
Level Tek II, Capacitance Level Switch
Pressing the [RT] pushbutton will begin the
procedure to recover the default settings. The
display will show:
CalibCLR
NO*
Pressing the [DN] pushbutton will access the
RESET feature. The display will show:
CalibCLR
RESET
After a short period of time the top line of the
display will scroll the message:
"Selecting RESET erase current settings and
calibration"
Pressing the [RT] pushbutton will complete the
procedure. The instrument will respond by
displaying:
Pressing the [LT] pushbutton twice will return the
instrument to the normal mode.
Page 16
INSTRUCTION MANUAL
909GF295
CalibCLR
DONE