Electrical Connection; Figure 3-5 Electrical Connections - Robertshaw 5318B Instruction Manual

Level tek ii
Table of Contents

Advertisement

MODEL 5318B
Level Tek II, Capacitance Level Switch
3.4 ELECTRICAL CONNECTIONS
The instrument chassis may be removed from
the housing for wiring installation by loosening
the three (3) captive mounting screws and
withdrawing the chassis straight out. In re-
installing the chassis assembly, make certain
that the probe connection pin is engaged in the
chassis receptacle.
All electrical connections should be made in
accordance with Figure 3.3 and any applicable
national, state and/or local codes. See
Specifications (Section II) for control relay
contact ratings.
Table 3.1
Electrical Connections
TB101 – Supply Power
GND
Earth Ground
AC Neutral/
NEU (-)
DC Negative
AC Hot/
HOT (+)
DC Positive
Table 3.2

Electrical Connection

TB102 – Relay Contacts
NC1
Normally Closed #1
COMM1
Common #1
NO1
Normally Open #1
NO2
Normally Open #2
COMM2
Common #2
NC2
Normally Closed #2
NC1
COMM1
NO1
N02
COMM2
NC2
NOTE: CONTROL RELAY CONTACT
DESIGNATIONS ARE SHOWN WITH
THE RELAY IN THE DE-ENERGIZED
CONDITION. THE RELAY IS
NORMALLY ENERGIZED AND
BECOMES DE-ENERGIZED WHEN
AN ALARM CONDITION IS

Figure 3-5 Electrical Connections

NOTE – Refer to drawing number
909HB918, Certified Print, Installation
Drawing, Model 5318B for complete
installation and wiring requirements.
Page 5
INSTRUCTION MANUAL
909GF295
GND
NEU (-)
HOT (+)
DETECTED.

Hide quick links: