Connecting Power To The Commcenter System; For 120 Vac Operation; For 240 Vac Operation; For 24 Vdc Operation - Federal Signal Corporation D1 Series Installation And Maintenance Manual

Table of Contents

Advertisement

Available languages

Available languages

Installation and Maintenance Manual

Connecting Power to the CommCenter System

Operating power is connected to the 300MB through the three-position, field-wiring terminal block located
at the back of the unit. Two knockout openings are provided. One knockout should be removed and provided
with a bushing through which the power lines can be routed into the field wiring compartment.

For 120 Vac Operation

The 300MB is factory-set for 120 Vac operation.

For 240 Vac Operation

See Figure 2 on page 11. Set switch SW1 on the motherboard to the

For 24 Vdc Operation

See Figure 10 on page 15. If using 24 Vdc either as a primary or auxiliary source of power, remove the
labeled jumper from terminals TB2-7 and TB2-8 of terminal block TB2, before using these positions.
Connect the " + " terminal of 24 Vdc power supply to the terminal TB2-8 (+24 Vdc) and "
24 Vdc power supply to the terminal TB2-7 (-24 Vdc) of the TB2 terminal block located in the back of the
300MB. Install a Class II power supply, such as a Federal Signal PS600, and its associated wiring.
16
QUALIFIED INSTALLERS ONLY — This device is to be installed by a trained
electrician who is thoroughly familiar with the National Electric Code and will
follow the NEC guidelines as well as local codes.
SHOCK HAZARD — Do not perform any installation or maintenance on this
system when power is on. Because the 300MB does not have a power switch,
ensure that the power is disconnected before proceeding. Failure to heed this
warning may cause serious injury or death.
CROSSTALK/INTERFERENCE HAZARD — Mixing power lines with signal lines
can cause cross talk, interference, or hum in the signal lines, which interferes
with the emergency warning capability of this equipment. Do not install power
lines in the same conduit as signal lines.
Model 300MB-SD CommCenter Series D1
240 V
position.
" terminal of the

Advertisement

Table of Contents
loading

This manual is also suitable for:

300mb-sd

Table of Contents