Contents Equipment Application Safety Location of Equipment Minimum Access Requirements for Maintenance Noise Levels Fresh Air Inlet and Exhaust Air Outlet Drainage Installation Instructions Unpacking and Inspection Unit Handling Lifting with a Crane Lifting with a Forklift Equipment Connections Ductwork Filters Electrical Requirements Mains Power Supply and Fusing...
HLI. Every proposed installation must be subject to an engineered design by a mechanical service consultant. Armcor Air Solutions is not responsible for the performance of equipment in applications for which the equipment was not designed or specified.
Location of Equipment It is important that the selected location for the equipment is suitable and can adequately accommodate the unit’s physical size, the unit weight and has safe and suitable access for correct operation and future maintenance requirements. Minimum Access Requirements Fresh Air Inlet for Maintenance •...
If damage is evident, it should be noted on the freight Wear safety goggles, work gloves, work boots and docket and contact is to be made with the Armcor protective clothing. Air Solutions sales office. A claim should be lodged •...
• The power requirement and voltage are detailed on for the specified air flow without excessive pressure the equipment technical specifications (available at armcor.com.au) and are on the identification/serial levels. The unit should be situated as close as possible to the point of use to prevent unnecessary number plate attached to each unit.
Standard Equipment Layout Condensor Dumpback Damper Supply Air Fresh Air Lifting Points Forklift Supports/ Lifting Points OAP – Outside Air Package Units Installation and Operation Manual 2021...
Features Oil Sight Glass TX Valve Oil should be visible during operation after the unit has All TX valves have adjustment for super heat settings. stabilised. 8-11K is acceptable for R407C and R410A gases. Compressor Control Board OAP – Outside Air Package Units Installation and Operation Manual 2021...
Page 10
Filter Dryer (Biflow type) Electrical Connection Must be replaced if the system is opened. Tighten all electrical connections before starting and commissioning unit. Drip Tray Drains All drains should be trapped externally to the unit. Phase Failure Fan Control Card. Relay Adjust pots for speed control of supply &...
• Armcor Air Solutions are pleased to provide expert • Cleanable Filters. advice on special service maintenance requirements If filters are cleanable, they should be cleaned once a for particular installations.
Warranty The Armcor Air Solutions Warranty Policy should be read in conjunction with the Terms and Conditions of Sale. These are available on our website armcor.com.au What The Warranty Policy Covers • Any warranty work performed by Armcor Air Solutions outside of Melbourne metro area will...
Pre-start Checklist Unit Installation and Connections Check that equipment is fully installed in accordance with the installation instructions Visually check that air flows will not be obstructed Electrical Visually check all field wiring Tighten all electrical connections including all factory wiring connections Ensure supply cable is the correct size Check that required supply voltage is available on all phases Check overload settings are correct (if applicable)
Commissioning Checklist General Air Filters: Overall Size and Number Drain Pipe Traps and Vents fitted to Indoor Unit as per Installation Instructions Y / N Drain is Clearing Water Properly Y / N Check Vibration of Outdoor Unit OK / EXCESSIVE Check Vibration of Indoor Unit OK / EXCESSIVE Belt Tensioning Adjusted...
Page 15
Commissioning Checklist Performance 1 Fresh Air Temperature °C DB °C WB 2 Supply Air Temperature °C DB °C WB Notes ....................................................................................................................................................................................................................................OAP – Outside Air Package Units Installation and Operation Manual 2021...