General features: 
DSE3‐23 HW and DSE3‐23 HQ are devices designed for acoustic and optical notice in fire alarm systems. 
All materials used to manufacture it comply with fire system requirements.  
The alarm device has to be installed by qualified personnel only, respecting all installation standards such as recommended 
distances and height in order to get the maximum efficiency.  
 
 
Coverage volume (wall) – CUBE light lens: 
Coverage volume (wall) – WIDE light lens: 
Category with WIDE lens or CUBE lens: 
Nominal Voltage supply 
Operating Voltage range 
Max Current consumption 
Max Power consumption 
Max current for sound 
Flash ‐ Strobo frequency 
Main sound frequency (average) 
Main sound pattern  
Max level SPL @1 m 
Available Patterns 
Available alarm timings 
Operating temperature 
Timing 
Command from the control panel 
Enclosure protection degree 
Size (HxLxW) 
Weight 
Standards 
 
              
 
DSE3‐23 HW, DSE3‐23 HQ 
Optical and acoustic fire alarm device for indoor installation 
S-287.1-DSE-ENG
DSE3-23 SERIES
              Optical and acoustic fire alarm device 
TECHNICAL DATA 
7 x 11 x 10 m (Height, Width, Distance) 
4 x 18 x 7 m (Height, Width, Distance) 
O (see coverage here above) 
24Vdc 
20Vdc ‐ 30Vdc  
130mA @Vdc=24V (DIP1=OFF 110mA, DIP1=ON 130mA) 
2.6W 
20mA +/‐5mA 
0.6Hz or 1.0Hz 
Sound 1 850Hz 
Sound 1 Decay from 500Hz to 1200Hz period 1,7s 
See Diagram 1 
6 available patterns: 2 modulated, 2 pulsed, 1 bitonal,1 continuous 
4 available timings: Infinite, 3 minutes, 8 minutes, 15 minutes 
From ‐10 °C to +55°C 
Programmable (see chart) 
Polarity inversion 
IP31C (Type A, for indoor use) 
155x100x53mm 
250 gr 
EN54‐3:2001 + A1:2002 + A2:2006, 
EN54‐23:2010 
Rev. A.1 10/2017
 
 

Advertisement

loading

Summary of Contents for Honeywell NOTIFIER DSE3-23 Series

  • Page 1   S-287.1-DSE-ENG Rev. A.1 10/2017 DSE3-23 SERIES               Optical and acoustic fire alarm device      DSE3‐23 HW, DSE3‐23 HQ    Optical and acoustic fire alarm device for indoor installation  General features:  DSE3‐23 HW and DSE3‐23 HQ are devices designed for acoustic and optical notice in fire alarm systems.  All materials used to manufacture it comply with fire system requirements.   The alarm device has to be installed by qualified personnel only, respecting all installation standards such as recommended  distances and height in order to get the maximum efficiency.       TECHNICAL DATA  Coverage volume (wall) – CUBE light lens:  7 x 11 x 10 m (Height, Width, Distance)  Coverage volume (wall) – WIDE light lens:  4 x 18 x 7 m (Height, Width, Distance)  Category with WIDE lens or CUBE lens:  O (see coverage here above)  Nominal Voltage supply  24Vdc  Operating Voltage range  20Vdc ‐ 30Vdc   Max Current consumption  130mA @Vdc=24V (DIP1=OFF 110mA, DIP1=ON 130mA)  Max Power consumption  2.6W  Max current for sound  20mA +/‐5mA  Flash ‐ Strobo frequency  0.6Hz or 1.0Hz  Main sound frequency (average)  Sound 1 850Hz ...
  • Page 2: Installation

    Installation:   1. Insert the head of a screwdriver in the slot as shown in Picture 2 and then press gently to lift the cover up a bit;  2. Take off the cover from the tracks;  3. Hang the sounder on the wall through the 4 fixing holes located on the sounder base (see Pict. 1) and using 4 pcs. of 5‐ mm wall plugs;  4. In case of system with external pipes, use an adapter to connect all cables;  5. Close the siren and fix the cover with the screw provided.                      Fixing  Fix the cover with the    Holes    screw                Insert the screwdriver    here to open the    sounder    Pict. 2    Pict. 1   ...
  • Page 3         DSE3‐23 HQ   The device is classified as O. It is designed to cover a maximum volume with side A = 7 m, side B = 10 m, side C = 11 m (See  Pict. 6).   It can be installed on a wall at an altitude of 7 m or on a ceiling at h = 10 m maximum.  For wall installation, the device must be installed with the long side perpendicular to the floor and the strobe flashing unit  looking downwards. Maximum installation height is 7 m, the illumination coverage will be 5,5 m on the right, 5,5 m on the  left and 10 m on front.  For ceiling installation, the device must be installed with the long side perpendicular to the wall and the strobe flashing unit  looking  towards  the  space  to  be  illuminated.  Consider  that  the  wall  on  the  side  without  flash  will  be  not  illuminated.  Maximum installation height is 10 m; the illumination coverage will be 7 m at the front, 5,5 m on the right and 5,5 m on the  left.      Pict. 6bis: mount the long side of the device    perpendicular with respect the wall of the room     ...
  • Page 4: Dip Switch

      Sounds chart:  Terminal  DIP 2  Sound  Priority  Modulation  Modulation limits (Hz)  S1 (1,2 and 3,4)  OFF  Sound 1  1  DIN (continuous and decreasing)  500 – 1.200  S2 (5 and 6)  OFF  Sound 2  2  NFS32 (continuous and alternated)  440 – 554  S3 (8 and 9)  OFF  Sound 3  3  ISO8021 (fixed tone with pauses)  520  S1(1,2 and 3,4)  ON  Sound 4  1  BS modified (fixed tones alternated)  520– 940  S2 (5 and 6)  ON  Sound 5  2  NEN2575 (increasing with pause)  500 – 1.200  S3 (8 and 9)  ON  Sound 6 ...
  • Page 5: Control Panel

    CHART 3: terminals connection  TERMINAL  Connection  S1 (1,2 and 3,4)  trigger for: sound 1 – sound 4   S2 (5 and 6)  trigger for: sound 2 – sound 5   SYNC (7)  Devices synchronism: panels and DSE3‐23 sirens. Connect to the other SYNC or B terminals  S3 (8 and 9)  trigger for: sound 3 – sound 6      CHART 2: DIP 3 – DIP 4, selection of alarm sound duration    DIP3  DIP4  Acoustic alarm duration    OFF  OFF  INFINITE (DEFAULT, COMPLYING TO EN54‐3)    ON  OFF  3 MINUTES (NOT COMPLYING TO EN54‐3)    OFF  ON  8 MINUTES (NOT COMPLYING TO EN54‐3)      ON  ON  15 MINUTES (NOT COMPLYING TO EN54‐3)    VOLUME and ABSORBED CURRENT adjustment:  Rotate trimmer P1 to adjust acoustic power        Pict. 7: connectors/terminals/trimmer ...
  • Page 6 081/7879159 - E-mail: notifier.napoli@notifier.it - 70125 Bari - Via Della Costituente, 29 - Tel.: 080/6180700 - Fax: 080/5648114 - E-mail: notifier.bari@notifier.it - 95126 Catania - Viale Alcide De Gasperi, 187 - Tel.: 095/2279511 - Fax: 095/7120753 - E-mail: notifier.catania@notifier.it Società Unipersonale soggetta ad Attività di Direzione e Coordinamento da parte di Honeywell International Inc.               ...