6150-ID Sharpshooter PIR
Installation Instructions
Walk test
A walk test mode for testing the unit operation and
coverage pattern is provided. Do the following to walk test
the unit:
1.
Ensure the unit is enrolled in the PinPoint system. The
walk test LED will not light unless the unit is enrolled.
2.
Pull the front cover away from the base until the
tamper switch opens to enable the walk test mode.
3.
When the unit is remounted on the base, the unit
remains in the walk test mode for 3 to 4 minutes. If
additional time is required, releasing and depressing
the tamper switch will reset the walk test timer.
Depending on pulse and sensitivity DIP switch
settings, the walk test mode allows the unit to alarm
whenever one or two curtain areas are entered. The
LED visible on the front cover lights to indicate an
alarm.
4.
Walk test the detection pattern and make any
necessary adjustments.
5.
Replace and walk test the unit to verify the unit is
communicating with the controller.
Note
After the walk test mode times out in 3 to 4
minutes, the unit returns to normal operating
mode. In normal operating mode, the unit
LED is disabled to reduce voltage loss on the
PinPoint bus.

Maintenance

When installed and used properly, the unit provides years
of service with minimal maintenance. To ensure proper
operation, you should walk test the unit annually (see
Walk test).
Clean the inside of the unit with a soft bristled brush or
compressed air. Clean the cover with a damp (water) cloth
as needed to keep it free of dust and dirt. Always test the
unit after cleaning.
Figure 11.
Dimensions
1.9 in.
(48 mm)
2.2 in.
(55 mm)
Front View
2.9 in.
(74 mm)
3.7 in.
(94 mm)
Top View
45°
Side View
2.4 in.
(61 mm)