Multiple sensor option (3)
m
(Using individual and/or dual sensor assemblies)
Sensor Redundancy
m
(Higher temperature of two operating sensors used)
Easy remote sense
m
(Electronic sensors, wired to control)
Smart manual reset
m
(Manual reset only if operating limit doesn't open)
Serviceman reset protection
m
(Latch-up after three consecutive lockouts
Power-independent lockout
m
(Power cycling won't reset from lockout or latch-up)
Diagnostic LED's
m
(Call for heat, and lockout/latchup)
SMC Technology
m
(1)
Latch-up mode shuts down the control after three consecutive lockouts, and requires a
special procedure to reset. This ensures the owner will call in a licensed technician to
troubleshoot and correct burner problems.
(2)
The 90320 provides two limit relays. Carlin's patented SMC technology (Safety Monitoring
Circuit) monitors the contacts of both relays. Lockout occurs if a limit relay contact is found
closed when it should be open.
)
(1)
(2)
with Sensor Redundancy
Specifications
Carlin's Model 90320 microprocessor-operated, multiple-contact tem-
perature limit controls are available as described below. The model
provides two contacts — one for operating limit and one for high limit.
Refer to separate product listing sheets for pre-defined models, or re-
quest a control to meet your specifications, within the available ranges
listed below.
90320
B
Control model
Control power input
(red-white wire)
Contacts
Motor load
Contact rating
General
Wires
Quantity
240
Hot / Neutral
VAC
Limits OUT
Adjustable oper. limit range
Fixed high limit temperature
Fixed differential (subtractive)
Operating temperature limits
Storage temperature limits
Agencies
©
Copyright 2021 – Carlin Combustion Technology
Carlin Combustion Technology
126 Bailey Road
Phone 203-680-9401
T
800-989-2275
ech support
Data sheet
Dual limit temperature control
• operating and high limit action
• smart manual reset on high limit
• operating limit sensors, redundant
• high limit sensor
• operating and limit contacts in series
B
240
, 50/60 hz, 12
VAC
VA
2 in series
240
, 50/60 hz, 1
VAC
HP
120/240
, 50/60 hz, 15
VAC
AMPS
3
red-white / white
black
Any range between 50°F to 240°F
Any value from 160°F to 240°F
Any value from 5°F to 100°F
+32°F to +140°F
–40°F to +185°F
North Haven, CT 06473
Fax 203-680-9403
carlincombustion.com

Advertisement

loading
Need help?

Need help?

Do you have a question about the EZ-Temp 90320 and is the answer not in the manual?

Questions and answers

Summary of Contents for Carlin EZ-Temp 90320

  • Page 1 North Haven, CT 06473 Phone 203-680-9401 Fax 203-680-9403 The 90320 provides two limit relays. Carlin’s patented SMC technology (Safety Monitoring Circuit) monitors the contacts of both relays. Lockout occurs if a limit relay contact is found closed when it should be open.
  • Page 2 Model 90320 Microprocessor Temperature Controls — Data sheet Model 90320 Button Press Instructions Diagnostic LED’s Reset Down Quickly press the UP or DOWN button to display water Display Mode LEGEND temperature. Press and hold UP and DOWN buttons for 5 seconds to enter Set Temp Mode Power Off “Set Temperature”...
  • Page 3 Model 90320 Microprocessor Temperature Controls — Data sheet Configurations Mounting – 90320 controls mount to any standard well. Mount the 90320 directly to a well (new or existing) with hardware sup- plied in the separate well mounting kit. Well Kits – Wells for 90320 sensors are available in the sizes shown below.
  • Page 4 Model 90320 Microprocessor Temperature Controls — Data sheet 90320B White , 50/60 , 50/60 CONNECTIONS AT APPLIANCE POWER TO APPLIANCE Red/White Appliance limits Service PERATING LIMT switch IGH LIMIT Dual limit OUT Black To operating limit sensor To high limit sensor To operating limit sensor MN90320B 080221...