Page 4
The heating portion of the RAYCHEM Mat shall not touch, cross over, or overlap itself . • Do not install RAYCHEM Mat in direct contact with or within 0 .256” (6 .5 mm) of any combustible surfaces or materials .
Page 5
Mats are designated UKXXYY-WWW where UK denotes the voltage XXYY is the dimensions in meters and WWW is the watt density in watts per square meter. e.g UK1509-160 is a 230V mat 1.5 x 0.9 meters in size and 160 w/m watt density .
4. Dry fit and route power lead path For concrete slab subfloors, RAYCHEM recommends Position RAYCHEM Mat to fit contours of room. Route a insulating the slab prior to installing RAYCHEM Mat . path for the power lead to the electrical box . The power Insulation will improve the upward heat transfer lead CANNOT cross over on top of RAYCHEM Mat.
Use 6 mm x 6 mm square notched trowel to spread 6 mm layer of flexible tile adhesive* onto subfloor. Work on one manageable section at a time . For RAYCHEM Mat installations in showers or wet locations, spread tile adhesive* onto sloped mortar bed above PVC (polyvinyl) pan liners .
Page 8
Refer to page 12 for sensor probe testing procedures. Duct tape the floor sensor probe on top of RAYCHEM Mat. The probe’s tip should be between the heating wires . Ensure the probe’s tip is located in an area that can represent the overall floor temperature and away from other heating/cooling sources (i.e.
SKIP TO PAGE 10. Do not use sharp tools or power tools to clean grout lines; doing so may damage RAYCHEM Mat . Use 6 mm x 6 mm square notched trowel to spread minimum 6 mm layer of flexible tile adhesive* on top of RAYCHEM Mat.
Refer to page 11 for insulation and resistance testing Use smooth trowel to spread minimum 6 mm layer of procedures . flexible tile adhesive* on top of RAYCHEM Mat. Ensure tile adhesive* layer is level and smooth . Self-leveling compounds may also be used . Allow tile adhesive* or self-leveller to cure as per manufacturer’s instructions.
INSULATION & RESISTANCE TESTING/MAT RESISTANCE LOG Note: RAYCHEM Mat must be tested before, during and after installation to validate the warranty. Insulation Test To ensure the heating wire is fully insulated: With a digital multimeter, set it to measure resistance/ohms. If using an ohmmeter, set it to the 200 ohm setting.
Page 12
INSULATION & RESISTANCE TESTING Testing Floor Sensor Probe Test To ensure the floor sensor probe is not damaged: With a digital multimeter (or ohmmeter), set the device to the 20KΩ (Kilohms) setting. Note: Some multimeters do not have the 20KΩ (Kilohms) setting. Find a suitable multimeter that has this setting. Place a multimeter clip on each of the wires.
RCD with trip rating 30mA maximum . The power leads of RAYCHEM Mat may need to be routed inside suitable conduit according to local electrical codes . Check with the local authority having jurisdiction to determine requirements.
C . Mats are designated UKXXYY-WWW where UK denotes the voltage XXYY is the dimensions in meters and WWW is the watt density in watts per square meter. e.g UK1509-160 is a 230V mat 1.5 x 0.9 meters in size and 160 w/m watt density .