Diagram of Controller

LOCATION OF CONTROL CARDS
CONTROL INPUT SIGNAL CONFIGURATION
Control
SW1
SW2
Type
4-20mA
On
On
4-20mA
On
On
4-20mA
1-5V
1-5V
Off
On
1-5V
2-10V
2-10V
Off
Off
2-10V
0-5V
Off
On
0-10V
Off
Off
Control Function
Normal
Log Rate*
J2
J1
Motor wire
J1T4
J1T3
J1T2
SW3
SW4
Loss of Signal Operation
On
On
Motor Off
On
Off
Close (Zero Setting)
Off
Off
Open (Span Setting)
On
On
Motor Off
On
Off
Close (Zero Setting)
Off
On
Open (Span Setting)
On
On
Motor Off
On
Off
Close (Zero Setting)
Off
On
Open (Span Setting)
Off
Off
N/A
Off
Off
N/A
Default Settings
SW5
* Log Rate control function averages rapidly changing input signals. It
Off
approaches position logarithmically by continuously varying duty cycle.
On
This has the effect of extending the actuator process time and can help in
applications where the PID control signal is not stable or causes the actuator
to constantly move to achieve a desired position.
Page 6 of 14 P2/3 24VDC Proportional Series
Page 6 of 14 P2/3 12VDC Proportional Series
Proportional Control
DMC-102 CONTROLLER
Dip Switches
XMA-105 FEEDBACK GENERATOR
Red Running
CCW (OPEN)
Indicator
SPAN
ZERO
Green Running
CW (CLOSED)
Indicator
Sensitivity
ZERO
4-20mA
out+
4-20mA
out-
SPAN