CONTINUOUS LOW SPEED FAN SEQUENCE OF OPERATION
MANUAL FAN SELECTION MADE AT THERMOSTAT.
AFTER 2 SECOND DELAY, INDOOR BLOWER IS
ENERGIZED ON CONTINUOUS FAN SPEED.
Y
E
S
Y
E
S
THERMOSTAT CALLS FOR FIRST STAGE COOL.
THERMOSTAT CALLS FOR FIRST-STAGE HEAT.
YES
YES
INDOOR BLOWER RAMPS TO FIRST STAGE
AFTER 45-SECOND DELAY, INDOOR BLOWER
COOLING SPEED AFTER A 2-SECOND DELAY.
SWITCHES TO LOW HEAT SPEED.
FIRST-STAGE COOL DEMAND SATISFIED?
FIRST-STAGE HEAT DEMAND SATISFIED.
YES
YES
NO
NO
SECOND STAGE COOL DEMAND
THERMOSTAT CALLS FOR SECOND-STAGE HEAT.
YES
INDOOR BLOWER RAMPS TO SECOND
INDOOR BLOWER SWITCHES TO HIGH HEAT SPEED
STAGE COOL SPEED
AFTER 30-SECOND RECOGNITION PERIOD.
YES
SECOND STAGE COOL DEMAND SATISFIED?
SECOND-STAGE HEAT DEMAND SATISFIED.
YES
YES
INDOOR BLOWER RAMPS DOWN TO FIRST STAGE
INDOOR BLOWER RAMPS DOWN TO LOW
COOL SPEED.
HEAT SPEED.